Inspections for the day of: Wednesday, July 15, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00756 ELE-Aging Inspection7/15/20157/15/20157/17/2015 3:49:21 PM CANC
too busy
ELE15-01604 Permanent Service7/15/20157/15/20157/15/2015 1:56:52 PMPPASS
Service inspection only Phone #: ###-#### Inspection requested via web by jamie berg p/s o/h rec ok
ELE15-02179 Electrical Rough-In7/15/20157/15/20157/15/2015 1:43:01 PMPPASS
This is the mattress sales area in the SEARS department store. Phone #: ###-#### Inspection requested via web by Spencer McLean Receptacle additions all fished in. Called contractor to ask about whether came off existing circuit or added circuits, No answer. Rough in ok
GCE15-00107 GCE-Rough-In7/15/20157/15/20157/15/2015 12:46:05 PMPPASS
Stephanie ###-#### Underground for post light rough in ok cover
GCE15-00106 GCE-Rough-In7/15/20157/15/20157/15/2015 12:30:27 PMPPASS
Stephanie ###-#### Post light conduit rough in ok cover
ELE15-02141 Final7/15/20157/15/20157/15/2015 11:50:09 AMPPASS
Final ok
ELE15-02141 Permanent Service7/14/20157/15/20157/15/2015 11:33:36 AMAPASS
Justin Phone #: ###-#### p/s u/g rec ok
ELE15-02162 Rough-In Permanent Service7/14/20157/15/20157/15/2015 10:44:31 AMAPASS
I''m sorry the trench caved in, it makes it hard to see the depth of conduit. But it is 18" and in addition they are going to add fill on top and sod. The grounds and neutrals are separated in the interior panel. Phone #: ###-#### Inspection requested via web by Craig Korell Underground rough in ok cover p/s u/g rec ok
ELE15-01957 Final7/14/20157/15/20157/15/2015 10:18:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Final ok
ELE15-01900 Rough-In Permanent Service7/13/20157/15/20157/15/2015 9:57:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Judy Spencer Elections entrance, 1st office to right behind reception desk. No service just office remodel. Wall rough in ok cover
ELE15-00768 Final7/14/20157/15/20157/15/2015 9:22:23 AMAFAIL
If the house is locked the code is 7105. call Lloyd at ###-#### for any questions Phone #: ###-#### Inspection requested via web by Jerry Moore BCC- Shall have access to all electrical in garage.
210.8- All receptacles in kitchen area serving counter top surfaces shall have GFCI protection. Pantry.
210.8 All receptacle outlets located with in 6' of sink shall have GFCI protection.
314.20- All boxes set back 1/4" or more in tile shall have an extension ring.
406.5(B)- Receptacles and boxes shall be secured and flush with finished surface.
422.30- Hood disconnecting means shall be accessible. Receptacle shall not be located behind fixed panel.
ELE15-02166 Temporary Service7/14/20157/15/20157/15/2015 8:37:16 AMAPASS
Phone #: ###-#### Inspection requested via web by kevin blackmon t/s u/g n ok