PLM15-01368
| Plumbing Rough-in | 7/15/2015 | 7/15/2015 | 7/16/2015 11:50:30 AM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steven smith=========1)PLUMB ALL HORIZONTAL WET VENTS PER 2009 ISPC. 2) ALL VENTS NEED TO BE LEVEL OR GRADED BACK. 3) AAV'S FOR ISLAND FIXTURES ONLY. 4) SUPPORT DWV EVERY 4' 5) 35 DFU'S ON 3" HORIZONTAL IS MAX,EJECTOR COUNTS AS 20 DFU'S. 6) DWV TEST FAIL. 7) MISSING NAIL PLATES. 8) NEED TO COMPLETE ALL ROUGH IN. CORRECTION NOTICE POSTED ONSITE.
|
PLM15-01314
| Final | 7/15/2015 | 7/15/2015 | 7/15/2015 4:25:33 PM | P | FAIL |
|
|
Call Perry for access and questions Phone #: ###-#### Inspection requested via web by Justin Whitt======WATER SOFTENER NEEDS AIRGAP ON DRAIN HOSE AT WASHER BOX, EXPANSION TANK NEEDS TO BE ON THE COLD SIDE.
|
PLM15-02365
| Groundwork | 7/15/2015 | 7/15/2015 | 7/15/2015 4:04:59 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy====18" PIPE FROM CONVEYOR OK
|
PLM15-02338
| Sprinkler (Final) | 7/15/2015 | 7/15/2015 | 7/15/2015 2:45:04 PM | P | PASS |
|
|
Inspection requested via web by thad cork
|
PLM15-02338
| Water and/or Sewer | 7/15/2015 | 7/15/2015 | 7/15/2015 2:44:38 PM | P | CANC |
|
|
Inspection requested via web by thad cork=====CANC BY JL AND CHANGED TO SPRINKLER FINAL
|
PLM15-02337
| Sprinkler (Final) | 7/15/2015 | 7/15/2015 | 7/15/2015 2:44:03 PM | P | PASS |
|
|
Inspection requested via web by thad cork
|
PLM15-02337
| Water and/or Sewer | 7/15/2015 | 7/15/2015 | 7/15/2015 2:43:49 PM | P | CANC |
|
|
Inspection requested via web by thad cork====CANC BY JL AND CHANGED TO SPRINKLER FINAL
|
PLM15-01410
| Plumbing Rough-in | 7/14/2015 | 7/15/2015 | 7/15/2015 2:23:59 PM | P | PASS |
|
|
MIKE IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
|
PLM15-02346
| Plumbing Rough-in | 7/14/2015 | 7/15/2015 | 7/15/2015 1:58:46 PM | P | FAIL |
|
|
plumbing rough inspection Lockbox code 4320 Don Beevers is contact Phone #: ###-#### Inspection requested via web by TERRY SIDWELL====WATER NOT UNDER TEST OR WORKING PRESSURE
|
PLM15-01047
| Final | 7/15/2015 | 7/15/2015 | 7/15/2015 1:38:27 PM | P | PART |
|
|
partial final - if questions call Matt @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann===PHASE 3 PREP SINK FINAL OK
|
PLM15-01371
| Groundwork | 7/14/2015 | 7/15/2015 | 7/15/2015 1:10:47 PM | P | PART |
|
|
DAVID IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER=====TD AND FD IN SERVICE OK
|
PLM15-01725
| Final | 7/15/2015 | 7/15/2015 | 7/15/2015 12:50:27 PM | P | PASS |
|
|
Backflow has been relocated, re-tested and temp mixing valves have been locked and tagged. Thanks. Scott. Phone #: ###-#### Inspection requested via web by Scott Sparrell=====CORRECTIONS MADE
|
MIS15-00159
| PLM-Final | 7/15/2015 | 7/15/2015 | 7/15/2015 12:30:56 PM | P | PASS |
|
|
CORRECTIONS MADE
|
PLM15-02294
| Plumbing Rough-in | 7/14/2015 | 7/15/2015 | 7/15/2015 12:20:09 PM | P | PASS |
|
|
JOB # 18065. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes====
|
PLM15-00618
| PLM-Aging Inspection | 7/15/2015 | 7/15/2015 | 7/15/2015 11:53:45 AM | | PASS |
|
|
PLM CONTRACTOR SAYS WSIP
|
PLM15-01822
| Plumbing Rough-in | 7/14/2015 | 7/15/2015 | 7/15/2015 11:24:35 AM | P | PASS |
|
|
JOB # 13118. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
|
PLM15-02352
| DOC - Permit Finaled | 7/15/2015 | 7/15/2015 | 7/15/2015 11:08:46 AM | P | PASS |
|
|
|
PLM15-02352
| Water and/or Sewer | 7/14/2015 | 7/15/2015 | 7/15/2015 11:08:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brett Simmons
|
PLM15-01286
| Final | 7/14/2015 | 7/15/2015 | 7/15/2015 10:36:39 AM | A | PASS |
|
|
Inspection requested via web by Erin Whiting
|
PLM15-02292
| Groundwork | 7/14/2015 | 7/15/2015 | 7/15/2015 10:04:10 AM | A | PASS |
|
|
Rich Phone #: ###-####
|
PLM15-02348
| Water and/or Sewer | 7/14/2015 | 7/15/2015 | 7/15/2015 9:36:18 AM | A | PASS |
|
|
TANK WATER TEST FOR 7/15====OK TO BACKFILL AROUND TANK OK, TANK DISCHARGE WAITING ON APPROVED PLANS RESUBMITTED TO ENGINEER AND CITY.
|
PLM15-02320
| Groundwork | 7/14/2015 | 7/15/2015 | 7/15/2015 9:33:52 AM | A | PASS |
|
|
Chad Lewis is journeyman on the job and his cell # is ###-#### Phone #: ###-#### Inspection requested via web by Candice Martin=====GW OK INSIDE BLDG ONLY,
|
PLM15-00860
| Final | 7/14/2015 | 7/15/2015 | 7/15/2015 9:17:45 AM | A | PASS |
|
|
To gain entrance if not open call for garage key pad # ###-#### or ###-#### Phone #: ###-#### Inspection requested via web by david colburn
|
PLM15-02334
| Water and/or Sewer | 7/14/2015 | 7/15/2015 | 7/15/2015 8:55:31 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Semsudin Konjuhovac
|
PLM15-02310
| Groundwork | 7/14/2015 | 7/15/2015 | 7/15/2015 8:53:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Rohricht
|
PLM15-02348
| Water and/or Sewer | 7/14/2015 | 7/15/2015 | 7/14/2015 4:05:04 PM | A | CANC |
|
|
Phone number above is for Matt if there are any questions Phone #: ###-#### Inspection requested via web by Carolyn Rowle
|