Inspections for the day of: Wednesday, July 15, 2015.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Little
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM15-01368 Plumbing Rough-in7/15/20157/15/20157/16/2015 11:50:30 AMPFAIL
Phone #: ###-#### Inspection requested via web by steven smith=========1)PLUMB ALL HORIZONTAL WET VENTS PER 2009 ISPC. 2) ALL VENTS NEED TO BE LEVEL OR GRADED BACK. 3) AAV'S FOR ISLAND FIXTURES ONLY. 4) SUPPORT DWV EVERY 4' 5) 35 DFU'S ON 3" HORIZONTAL IS MAX,EJECTOR COUNTS AS 20 DFU'S. 6) DWV TEST FAIL. 7) MISSING NAIL PLATES. 8) NEED TO COMPLETE ALL ROUGH IN. CORRECTION NOTICE POSTED ONSITE.
PLM15-01314 Final7/15/20157/15/20157/15/2015 4:25:33 PMPFAIL
Call Perry for access and questions Phone #: ###-#### Inspection requested via web by Justin Whitt======WATER SOFTENER NEEDS AIRGAP ON DRAIN HOSE AT WASHER BOX, EXPANSION TANK NEEDS TO BE ON THE COLD SIDE.
PLM15-02365 Groundwork7/15/20157/15/20157/15/2015 4:04:59 PMPPART
Phone #: ###-#### Inspection requested via web by Brent Lacy====18" PIPE FROM CONVEYOR OK
PLM15-02338 Sprinkler (Final)7/15/20157/15/20157/15/2015 2:45:04 PMPPASS
Inspection requested via web by thad cork
PLM15-02338 Water and/or Sewer7/15/20157/15/20157/15/2015 2:44:38 PMPCANC
Inspection requested via web by thad cork=====CANC BY JL AND CHANGED TO SPRINKLER FINAL
PLM15-02337 Sprinkler (Final)7/15/20157/15/20157/15/2015 2:44:03 PMPPASS
Inspection requested via web by thad cork
PLM15-02337 Water and/or Sewer7/15/20157/15/20157/15/2015 2:43:49 PMPCANC
Inspection requested via web by thad cork====CANC BY JL AND CHANGED TO SPRINKLER FINAL
PLM15-01410 Plumbing Rough-in7/14/20157/15/20157/15/2015 2:23:59 PMPPASS
MIKE IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
PLM15-02346 Plumbing Rough-in7/14/20157/15/20157/15/2015 1:58:46 PMPFAIL
plumbing rough inspection
Lockbox code 4320
Don Beevers is contact Phone #: ###-#### Inspection requested via web by TERRY SIDWELL====WATER NOT UNDER TEST OR WORKING PRESSURE
PLM15-01047 Final7/15/20157/15/20157/15/2015 1:38:27 PMPPART
partial final - if questions call Matt @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann===PHASE 3 PREP SINK FINAL OK
PLM15-01371 Groundwork7/14/20157/15/20157/15/2015 1:10:47 PMPPART
DAVID IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER=====TD AND FD IN SERVICE OK
PLM15-01725 Final7/15/20157/15/20157/15/2015 12:50:27 PMPPASS
Backflow has been relocated, re-tested and temp mixing valves have been locked and tagged. Thanks. Scott. Phone #: ###-#### Inspection requested via web by Scott Sparrell=====CORRECTIONS MADE
MIS15-00159 PLM-Final7/15/20157/15/20157/15/2015 12:30:56 PMPPASS
CORRECTIONS MADE
PLM15-02294 Plumbing Rough-in7/14/20157/15/20157/15/2015 12:20:09 PMPPASS
JOB # 18065. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes====
PLM15-00618 PLM-Aging Inspection7/15/20157/15/20157/15/2015 11:53:45 AM PASS
PLM CONTRACTOR SAYS WSIP
PLM15-01822 Plumbing Rough-in7/14/20157/15/20157/15/2015 11:24:35 AMPPASS
JOB # 13118. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
PLM15-02352 DOC - Permit Finaled7/15/20157/15/20157/15/2015 11:08:46 AMPPASS
PLM15-02352 Water and/or Sewer7/14/20157/15/20157/15/2015 11:08:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Brett Simmons
PLM15-01286 Final7/14/20157/15/20157/15/2015 10:36:39 AMAPASS
Inspection requested via web by Erin Whiting
PLM15-02292 Groundwork7/14/20157/15/20157/15/2015 10:04:10 AMAPASS
Rich Phone #: ###-####
PLM15-02348 Water and/or Sewer7/14/20157/15/20157/15/2015 9:36:18 AMAPASS
TANK WATER TEST FOR 7/15====OK TO BACKFILL AROUND TANK OK, TANK DISCHARGE WAITING ON APPROVED PLANS RESUBMITTED TO ENGINEER AND CITY.
PLM15-02320 Groundwork7/14/20157/15/20157/15/2015 9:33:52 AMAPASS
Chad Lewis is journeyman on the job and his cell # is ###-#### Phone #: ###-#### Inspection requested via web by Candice Martin=====GW OK INSIDE BLDG ONLY,
PLM15-00860 Final7/14/20157/15/20157/15/2015 9:17:45 AMAPASS
To gain entrance if not open call for garage key pad # ###-#### or ###-#### Phone #: ###-#### Inspection requested via web by david colburn
PLM15-02334 Water and/or Sewer7/14/20157/15/20157/15/2015 8:55:31 AMAPASS
Phone #: ###-#### Inspection requested via web by Semsudin Konjuhovac
PLM15-02310 Groundwork7/14/20157/15/20157/15/2015 8:53:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Brandon Rohricht
PLM15-02348 Water and/or Sewer7/14/20157/15/20157/14/2015 4:05:04 PMACANC
Phone number above is for Matt if there are any questions Phone #: ###-#### Inspection requested via web by Carolyn Rowle