Inspections for the day of: Monday, July 15, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02467 Electrical Rough-In7/15/20197/15/20197/15/2019 3:13:48 PMPPASS
Cal- inspection for ground wire Phone #: ###-####
Grounding electrode conductor rough in ok cover
ELE19-02603 Permanent Service7/14/20197/15/20197/15/2019 2:35:00 PMPPASS
We will have Idaho Power disconnecting at 8am and will be ready for inspection shortly after noon. Phone #: ###-#### Inspection requested via web by Casey Fouts p/s o/h rec ok
ELE19-02357 Temporary Service7/15/20197/15/20197/15/2019 2:11:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-02216 Temporary Service7/15/20197/15/20197/15/2019 2:11:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-02608 Temporary Service7/15/20197/15/20197/15/2019 1:58:54 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Ground box broke. t/s u/g n ok
ELE19-01293 Final7/15/20197/15/20197/15/2019 1:52:39 PMPPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE19-01662 Final7/15/20197/15/20197/15/2019 1:01:53 PMAPASS
Inspection requested via web by brian morrow Final ok
ELE19-02588 Permanent Service7/12/20197/15/20197/15/2019 10:29:44 AMAPASS
Please call Nicole in advance at ###-####. Thanks again! Phone #: ###-#### Inspection requested via web by Rex Boyles
110.26- Clear egress and work space shall be present for all panel and electrical equipment by final. Remove all boxes, old equipment, and fuel cans.
p/s u/g rec ok
ELE19-02597 Rough-In Permanent Service7/12/20197/15/20197/15/2019 9:44:24 AMAPASS
Please contact when done Phone #: ###-#### Inspection requested via web by Thomas wilson

Address not posted.
Underground rough in ok cover p/s u/g rec ok
ELE19-02595 Electrical Rough-In7/12/20197/15/20197/15/2019 9:34:40 AMAPASS
Lock box code 8463. Walls inspection. Phone #: ###-#### Inspection requested via web by Dean Gernaat
Conference room no floor receptacle required room not 12' of wider.
Rough in ok cover
ELE19-02601 Rough-In Permanent Service7/12/20197/15/20197/15/2019 9:16:30 AMAPASS
Ready for Inspection. Prefer Monday morning inspection if possible. If not available please inspect in afternoon Phone #: ###-#### Inspection requested via web by Paula Gratiot Rough in ok cover p/s u/g n ok
ELE19-01527 Final7/12/20197/15/20197/15/2019 8:26:54 AMAFAIL
garage code 7530 Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3 Corrections not complete. Master bathroom left GFI hot right receptacle cold, up bathroom receptacle also cold, Main bath receptacles hot.