Inspections for the day of: Wednesday, July 16, 1997.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-02101 INSP - T/S and Final7/15/19977/16/19977/16/1997 12:00:00 AMAPASS
07/16/97 336 - ok
ELE97-02292 INSP - T/S and Final7/15/19977/16/19977/16/1997 12:00:00 AMAFAIL
07/16/97 336 - reinspection disapproved neutran connected to grounding bus
ELE97-02323 INSP - Electrical Rough-In7/15/19977/16/19977/16/1997 12:00:00 AMAPART
07/16/97 336 - ok
ELE97-01169 INSP - Electrical Rough-In7/15/19977/16/19977/16/1997 12:00:00 AMAFAIL
07/16/97 336 - ready to put drywall disapproved bath circuit not 20 A
ELE97-01426 INSP - Ele Rough-In/Perm Svc7/16/19977/16/19977/16/1997 12:00:00 AMPFAIL
07/16/97 336 - New jenny Craig store posted stop work temp wiring not cords
ELE97-01772 INSP - Final7/16/19977/16/19977/16/1997 12:00:00 AMPFAIL
07/16/97 336 - disapproved 113-3 225-18 250-92 250-113 110-14b 230-28 41
ELE97-02333 INSP - Electrical Rough-In7/16/19977/16/19977/16/1997 12:00:00 AMPPASS
07/16/97 336 - ok
ELE97-02338 INSP - Electrical Rough-In7/16/19977/16/19977/16/1997 12:00:00 AMPFAIL
07/16/97 336 - disapproved box fill