Inspections for the day of: Wednesday, July 16, 2003.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01197 FIRE-Final Inspection7/15/20037/16/20037/17/2003 12:00:00 AMAPASS
BLD02-01198 FIRE-Final Inspection7/15/20037/16/20037/17/2003 12:00:00 AMAPASS
BLD02-01199 FIRE-Final Inspection7/15/20037/16/20037/17/2003 12:00:00 AMAPASS
FIR03-00233 INSP-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 7/15/2003 at 6:51:11 PM. Contact: ###-####.
(This is a rough-in inspection) Sprinkler coverage is lacking (IFC 903.3.1.1)
Lack access to verifiy existing riser, system supervision and flow, signage and current annual system inspection. (JWA)
BLD02-03039 FIRE-Alarm Testing7/16/20037/16/20037/16/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 7/16/2003 at 7:26:48 AM. Contact: ###-####. will be rescheduled 7/16/2003 12:03:00 PM
BLD03-00864 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMAPASS
JACK; Phone #: ###-#### Internet Inspection Request from: Dixie Fellows this building is not sprinklered as shown on plans; okay to occupy 7/16/2003 8:36:50 AM
BLD03-01198 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMACANC
JEFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD03-01198 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMACANC
JEFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD03-01199 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMACANC
JEFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD03-01197 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMACANC
JEFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00124 INSP-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMAPASS
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD02-03053 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMAFAIL
jed - ###-#### shell permit not signed off; will need address and suite numbers 7/16/2003 8:35:59 AM
BLD02-02435 FIRE-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMAFAIL
need to complete fire alarms; see alarm permit corrections; overhead door didn't release with detectors; need to test emergency and exit lighting; door hardware from show room not openable from the inside without special knowledge; fusiblelinks painted on overhead doors; need sign on riser/FACP door 7/16/2003 11:26:10 AM
FIR03-00365 INSP-Final Inspection7/15/20037/16/20037/16/2003 12:00:00 AMAFAIL
don possibly #104; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need to reschedule - both doors were locked - couldn't gain entry 7/16/2003 2:36:20 PM
BLD02-02148 FIRE-Conference7/15/20037/16/20037/16/2003 12:00:00 AMPPART
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore met with GC about door hardware for nortwest exit (openable from the inside without special knowledge); extinguishers; remote LED's for duct detectors needed 7/16/2003 3:16:44 PM
FIR03-00134 INSP-Conference7/16/20037/16/20037/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 7/16/2003 at 7:35:24 AM. Contact: ###-####. UG flush okay 7/16/2003 12:54:07 PM
FIR03-00134 INSP-Sprinkler Rough-in/Hydro7/16/20037/16/20037/16/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 7/16/2003 at 7:36:11 AM. Contact: ###-####. UG flush okay 7/16/2003 12:54:17 PM
FIR02-00452 INSP-Final Inspection7/16/20037/16/20037/16/2003 12:00:00 AMPCANC
troy; Phone #: ###-#### Internet Inspection Request from: Dixie Fellows received a call from Troy of TVFP and he said he will reschedule for later this week 7/16/2003 8:35:25 AM
BLD02-01556 FIRE-Final Inspection7/16/20037/16/20037/16/2003 12:00:00 AMPPASS
ralph; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD02-01557 FIRE-Final Inspection7/16/20037/16/20037/16/2003 12:00:00 AMPPASS
ralph; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR02-00459 INSP-Final Inspection7/16/20037/16/20037/16/2003 12:00:00 AMPPART
need tape removed from all heads; need fire marshall tag on riser; escutcheons; sign on riser room door 7/16/2003 11:28:23 AM
FIR03-00057 INSP-Final Inspection7/16/20037/16/20037/16/2003 12:00:00 AMPFAIL
need map at FACP; sign on FACP door; descriptors for flows and devices; need breaker location and lockout on breaker; shunt for elevator not working; overhead doors not releasing; need record of completion 7/16/2003 11:30:30 AM
FIR03-00186 INSP-Sprinkler Rough-in7/16/20037/16/20037/16/2003 12:00:00 AMPFAIL
performed a walk through while doing the UG flush; need approved plans; heads obstructed by soffit in main lobby/counter; heads taped in west bay throughout 7/16/2003 12:56:58 PM
BLD02-02951 FIRE-Final Inspection7/16/20037/16/20037/16/2003 12:00:00 AMPPASS