ELE07-01601
| Final | 7/16/2007 | 7/16/2007 | 7/16/2007 3:30:21 PM | P | PASS |
|
|
MONTY Phone #: ###-#### ok to final, signed occ card
|
ELE07-00862
| Final | 7/16/2007 | 7/16/2007 | 7/16/2007 2:56:10 PM | P | PASS |
|
|
looked at sign, ok to final
|
ELE07-01601
| Electrical Rough-In | 7/16/2007 | 7/16/2007 | 7/16/2007 2:14:23 PM | P | PASS |
|
|
MONTY NOTE: UNDERGROUND Phone #: ###-#### u/g ok to cover
|
ELE07-02259
| Final | 7/16/2007 | 7/16/2007 | 7/16/2007 2:03:27 PM | P | NH |
|
|
rocky Phone #: ###-#### called contr, left card, told no address, fee due
|
ELE07-02268
| Final | 7/16/2007 | 7/16/2007 | 7/16/2007 1:35:38 PM | P | PASS |
|
|
CONTACT: JOHN OSTOLASA Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to final
|
ELE07-00791
| Final | 7/16/2007 | 7/16/2007 | 7/16/2007 12:54:01 PM | P | FAIL |
|
|
DUANE Phone #: ###-#### called, left corr notice, BCC all work shall be completed-plates on switches and recpts, disposal wired, nec 404.9 and 406.5 switch and recpt plates shall seat against mounting surface, 440.4 overcurrent device for a/c shall not exceed mfgrs nameplate rating, 110.3(B) shall install devices per instructions with listing- no reverse polarity
|
ELE07-02462
| Electrical Rough-In | 7/13/2007 | 7/16/2007 | 7/16/2007 10:43:47 AM | A | PASS |
|
|
Ron Chaney is the electrician Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok
|
ELE07-02462
| Final | 7/16/2007 | 7/16/2007 | 7/16/2007 10:43:19 AM | A | PASS |
|
|
Ron Chaney is the electrician Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final
|
ELE07-02487
| Electrical Rough-In | 7/16/2007 | 7/16/2007 | 7/16/2007 10:35:47 AM | A | FAIL |
|
|
need cover inspection in exposed areas, added recessed cans are cut in through existing sheetrock in dining and entry areas Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called, left message, left corr notice, nec 110.12(C) there shall be no broken parts or equipment, i.e. box shall not have clamps broken out, nm cable shall not have damaged jacketing, 300.4(D) nm cable shall be 1 1/4" from edge of framing member
|
ELE07-01544
| Electrical Rough-In | 7/13/2007 | 7/16/2007 | 7/16/2007 10:08:23 AM | A | PASS |
|
|
trent - ceilings only Phone #: ###-#### corrections made, ceilings only ok to cover
|
ELE07-02453
| Electrical Rough-In | 7/13/2007 | 7/16/2007 | 7/16/2007 9:40:14 AM | A | PART |
|
|
lloyd Phone #: ###-#### room 306 u/g and walls only ok to cover
|
ELE07-01271
| Conference | 7/13/2007 | 7/16/2007 | 7/16/2007 9:01:42 AM | A | DONE |
|
|
ken Phone #: ###-#### - please call 15 min prior to inspection talked about clear space at panel afci for bedroom , gfci for bath 1 1/4" holes, wire, when to come back for ri, ensure home-owner does wiring, not friend
|
ELE07-01310
| Final | 7/13/2007 | 7/16/2007 | 7/16/2007 8:38:03 AM | A | PASS |
|
|
TIM Phone #: ###-#### ok to final
|
ELE07-01187
| Final | 7/13/2007 | 7/16/2007 | 7/16/2007 8:23:35 AM | A | PASS |
|
|
TIM Phone #: ###-#### ok to final
|
ELE07-01071
| Final | 7/13/2007 | 7/16/2007 | 7/16/2007 8:04:50 AM | A | PASS |
|
|
TIM Phone #: ###-#### ok to final
|