Inspections for the day of: Monday, July 16, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01601 Final7/16/20077/16/20077/16/2007 3:30:21 PMPPASS
MONTY Phone #: ###-#### ok to final, signed occ card
ELE07-00862 Final7/16/20077/16/20077/16/2007 2:56:10 PMPPASS
looked at sign, ok to final
ELE07-01601 Electrical Rough-In7/16/20077/16/20077/16/2007 2:14:23 PMPPASS
MONTY NOTE: UNDERGROUND Phone #: ###-#### u/g ok to cover
ELE07-02259 Final7/16/20077/16/20077/16/2007 2:03:27 PMPNH
rocky Phone #: ###-#### called contr, left card, told no address, fee due
ELE07-02268 Final7/16/20077/16/20077/16/2007 1:35:38 PMPPASS
CONTACT: JOHN OSTOLASA Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to final
ELE07-00791 Final7/16/20077/16/20077/16/2007 12:54:01 PMPFAIL
DUANE Phone #: ###-#### called, left corr notice, BCC all work shall be completed-plates on switches and recpts, disposal wired, nec 404.9 and 406.5 switch and recpt plates shall seat against mounting surface, 440.4 overcurrent device for a/c shall not exceed mfgrs nameplate rating, 110.3(B) shall install devices per instructions with listing- no reverse polarity
ELE07-02462 Electrical Rough-In7/13/20077/16/20077/16/2007 10:43:47 AMAPASS
Ron Chaney is the electrician Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok
ELE07-02462 Final7/16/20077/16/20077/16/2007 10:43:19 AMAPASS
Ron Chaney is the electrician Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final
ELE07-02487 Electrical Rough-In7/16/20077/16/20077/16/2007 10:35:47 AMAFAIL
need cover inspection in exposed areas, added recessed cans are cut in through existing sheetrock in dining and entry areas Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called, left message, left corr notice, nec 110.12(C) there shall be no broken parts or equipment, i.e. box shall not have clamps broken out, nm cable shall not have damaged jacketing, 300.4(D) nm cable shall be 1 1/4" from edge of framing member
ELE07-01544 Electrical Rough-In7/13/20077/16/20077/16/2007 10:08:23 AMAPASS
trent - ceilings only Phone #: ###-#### corrections made, ceilings only ok to cover
ELE07-02453 Electrical Rough-In7/13/20077/16/20077/16/2007 9:40:14 AMAPART
lloyd Phone #: ###-#### room 306 u/g and walls only ok to cover
ELE07-01271 Conference7/13/20077/16/20077/16/2007 9:01:42 AMADONE
ken Phone #: ###-#### - please call 15 min prior to inspection talked about clear space at panel afci for bedroom , gfci for bath 1 1/4" holes, wire, when to come back for ri, ensure home-owner does wiring, not friend
ELE07-01310 Final7/13/20077/16/20077/16/2007 8:38:03 AMAPASS
TIM Phone #: ###-#### ok to final
ELE07-01187 Final7/13/20077/16/20077/16/2007 8:23:35 AMAPASS
TIM Phone #: ###-#### ok to final
ELE07-01071 Final7/13/20077/16/20077/16/2007 8:04:50 AMAPASS
TIM Phone #: ###-#### ok to final