BLD09-01567
| BLD-Final | 7/13/2012 | 7/16/2012 | 7/25/2012 5:21:30 PM | P | PASS |
|
|
Correction items verified. Life safety inspection passed.
|
FIR12-00246
| INSP-Sprinkler Rough-in | 7/16/2012 | 7/16/2012 | 7/16/2012 4:22:16 PM | P | PART |
|
|
Completed inspection for tenting at the east wing. Noted three areas in need of adjustment- notified general contractor. Also discussed FDC location to comply with IFC section 912 conditions.
|
FIR12-00314
| INSP-Final Inspection | 7/12/2012 | 7/16/2012 | 7/16/2012 3:25:03 PM | P | PART |
|
|
This is a partial final, just checking the office part. Richard is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
BLD11-00179
| FIRE-Final Inspection | 7/13/2012 | 7/16/2012 | 7/16/2012 3:24:29 PM | P | PASS |
|
|
|
BLD12-01529
| FIRE-Final Inspection | 7/16/2012 | 7/16/2012 | 7/16/2012 3:24:07 PM | P | FAIL |
|
|
Interior lighting at several locations is powered with the use of multiple extension cords. See IFC 2009 sec. 605.5 and 605.9 for details. Also need to remove merchandise displays blocking the marked exit doors. Post fire extinguisher as discussed.
|
BLD11-00179
| FIRE-Final Inspection | 7/13/2012 | 7/16/2012 | 7/16/2012 1:36:05 PM | A | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR11-00442
| INSP-Final Inspection | 7/16/2012 | 7/16/2012 | 7/16/2012 1:34:20 PM | P | PASS |
|
|
Corrections and remainder of acceptance testing completed satisfactory. Fire alarm permit finaled.
|
FIR11-00496
| INSP-Final Inspection | 7/13/2012 | 7/16/2012 | 7/16/2012 1:32:21 PM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection and walkthrough.
|
FIR12-00332
| INSP-Supply line flush | 7/13/2012 | 7/16/2012 | 7/16/2012 12:52:10 PM | A | FAIL |
|
|
Field installation does not match approved plans. The water meter appears to be upstream of the point of connection, line size does not correlate, noted ten additional fitting- 6 (90's) 4 (45's) in the supply line. Need to resubmit plans and calculations supporting field modifications. Also noted insufficient pipe support due to large gaps and voids in the trench. Backfill methods to meet NFPA 13 10.9.1, 10.9.2.
|