Inspections for the day of: Tuesday, July 16, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00116 INSP-Final Inspection7/15/20137/16/20137/16/2013 5:59:45 PMPPART
Concluded satisfactory 24 hr. pneumatic test of the new dry system with no pressure loss at the guage. Also finished the remainder of overhead inspection with the exception of the drop ceiling pendents at conf. room 107. Noted one overspaced upright to be relocated.
FIR13-00294 INSP-Final Inspection7/16/20137/16/20137/16/2013 5:55:49 PMPPASS
Noted correction items completed. Hood suppression system operated correctly under test conditions. Permit finaled.
FIR13-00110 INSP-Final Inspection7/15/20137/16/20137/16/2013 5:54:30 PMAFAIL
Need to provide WP notification devices at the guest room bathrooms per review notes, HT supervision and CO devices are not yet installed, field install does not correlate to the approved plan with regard to which rooms are ADA/hearing impared and provided with visual coverage, wall mount notification appliances should not be installed in a ceiling mount position. No testing performed due to modifications and adjustments necessary.
FIR13-00148 INSP-Final Inspection7/15/20137/16/20137/16/2013 5:41:09 PMANR
BLD12-03273 FIRE-Final Inspection7/15/20137/16/20137/16/2013 5:40:18 PMANR
Project is not in condition for fire life safety final at this time. Finishes underway, project related fire alarm work incomplete.
BLD13-00821 FIRE-Final Inspection7/16/20137/16/20137/16/2013 2:55:45 PMAPASS
Fire life safety passed. No access to fire sprinkler riser room- contractor to provide verification the existing system is current with an annual certification as discussed.
FIR13-00214 INSP-Sprinkler Rough-in/Hydro7/15/20137/16/20137/16/2013 1:31:21 PMAPART
Begin 24 hr air test of the new dry system at 10:30 AM @ 47psig.
FIR13-00175 INSP-Final Inspection7/15/20137/16/20137/16/2013 1:30:44 PMAPART
UG hydrostatic testing completed satisfactory.
BLD13-01454 FIRE-Final Inspection7/15/20137/16/20137/16/2013 11:34:53 AMAPASS
Life safety passed provided manual thumbturns at the main entry/exit are removed and signage is posted per permit documents. To be verified at structural final as discussed.