FIR13-00116
| INSP-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 5:59:45 PM | P | PART |
|
|
Concluded satisfactory 24 hr. pneumatic test of the new dry system with no pressure loss at the guage. Also finished the remainder of overhead inspection with the exception of the drop ceiling pendents at conf. room 107. Noted one overspaced upright to be relocated.
|
FIR13-00294
| INSP-Final Inspection | 7/16/2013 | 7/16/2013 | 7/16/2013 5:55:49 PM | P | PASS |
|
|
Noted correction items completed. Hood suppression system operated correctly under test conditions. Permit finaled.
|
FIR13-00110
| INSP-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 5:54:30 PM | A | FAIL |
|
|
Need to provide WP notification devices at the guest room bathrooms per review notes, HT supervision and CO devices are not yet installed, field install does not correlate to the approved plan with regard to which rooms are ADA/hearing impared and provided with visual coverage, wall mount notification appliances should not be installed in a ceiling mount position. No testing performed due to modifications and adjustments necessary.
|
FIR13-00148
| INSP-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 5:41:09 PM | A | NR |
|
|
|
BLD12-03273
| FIRE-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 5:40:18 PM | A | NR |
|
|
Project is not in condition for fire life safety final at this time. Finishes underway, project related fire alarm work incomplete.
|
BLD13-00821
| FIRE-Final Inspection | 7/16/2013 | 7/16/2013 | 7/16/2013 2:55:45 PM | A | PASS |
|
|
Fire life safety passed. No access to fire sprinkler riser room- contractor to provide verification the existing system is current with an annual certification as discussed.
|
FIR13-00214
| INSP-Sprinkler Rough-in/Hydro | 7/15/2013 | 7/16/2013 | 7/16/2013 1:31:21 PM | A | PART |
|
|
Begin 24 hr air test of the new dry system at 10:30 AM @ 47psig.
|
FIR13-00175
| INSP-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 1:30:44 PM | A | PART |
|
|
UG hydrostatic testing completed satisfactory.
|
BLD13-01454
| FIRE-Final Inspection | 7/15/2013 | 7/16/2013 | 7/16/2013 11:34:53 AM | A | PASS |
|
|
Life safety passed provided manual thumbturns at the main entry/exit are removed and signage is posted per permit documents. To be verified at structural final as discussed.
|