ELE12-01368
| ELE-Aging Inspection | 7/16/2015 | 7/16/2015 | 7/20/2015 6:37:35 AM | | DONE |
|
|
too busy
|
ELE13-01341
| ELE-Aging Inspection | 7/16/2015 | 7/16/2015 | 7/20/2015 6:37:14 AM | | DONE |
|
|
too busy
|
ELE15-02182
| Electrical Rough-In | 7/15/2015 | 7/16/2015 | 7/16/2015 4:11:15 PM | P | PASS |
|
|
Please call ###-#### before arriving as no one will be there till after 3:00 pm. Thank you Phone #: ###-#### Inspection requested via web by Cortney Hopper r/i ok kitchen and wet bar area
|
ELE15-02202
| Final | 7/16/2015 | 7/16/2015 | 7/16/2015 3:41:13 PM | P | PASS |
|
|
Matt Murrey is contact at ###-####. final for Meyers cabinet on 9th ; Broad St. Ped Signal... Phone #: ###-#### Inspection requested via web by Debby Pierce final ok
|
ELE15-02202
| Permanent Service | 7/16/2015 | 7/16/2015 | 7/16/2015 3:40:18 PM | P | PASS |
|
|
Matt Murrey is contact at ###-####. final for Meyers cabinet on 9th ; Broad St. Ped Signal... Phone #: ###-#### Inspection requested via web by Debby Pierce p/s u/g n ok (2 meters)
|
ELE15-01982
| Final | 7/16/2015 | 7/16/2015 | 7/16/2015 3:20:53 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve cooper final ok Please call when lift electrical and compressor hook up is complete Rex ###-####
|
ELE15-01257
| Electrical Rough-In | 7/16/2015 | 7/16/2015 | 7/16/2015 2:52:33 PM | P | PASS |
|
|
Wall cover. Dan Lowry is the on site contact. Phone #: ###-#### Inspection requested via web by Buster Bowen r/i walls ok except fire riser room
|
ELE15-02152
| Conference | 7/16/2015 | 7/16/2015 | 7/16/2015 2:21:45 PM | P | DONE |
|
|
Tyson - ###-#### Phone #: ###-#### Inspection requested via web by Matthew White Discuss reusing existing 2 inch feeder. Ok to reuse if raceway is clean and new THWN conductors are installed with ground conductor. Also discussed installation of new 400 amp main switchboard to relocate misc. main disconnects and clean up busy wall with code violations. OK to build platform to satisfy height requirements for oovercurrent devices maximum 6' 7"
|
ELE14-03333
| Final | 7/15/2015 | 7/16/2015 | 7/16/2015 12:24:42 PM | A | PART |
|
|
Contact: Jeremy Thornock Phone #: ###-#### Inspection requested via web by Deb Gooden final ok wing 1 2nd flr rms. and corridor. Rms. 200 thru 202, 229,231 thru 233,235 thru 241
|
ELE13-01291
| Final | 7/13/2015 | 7/16/2015 | 7/16/2015 11:25:28 AM | A | PART |
|
|
PLease contact Brandon Robinson for level 6 ; 7 inspection. Phone #: ###-#### Inspection requested via web by Tom Betty final ok corrections made for 1st floor kitchen island and lockoffs on hand dryers and GFCI protection on drinking fountains and all 120 volt receptacles , 2nd floor sound wall in office, 6th floor 100% and all rooftop on 7 and 8. All exterior GFCI's are now W.R. and ok
|
ELE15-01617
| Electrical Rough-In | 7/15/2015 | 7/16/2015 | 7/16/2015 9:44:02 AM | A | PASS |
|
|
Ron Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok underslab conduits from main electric rm. to the east electric rm.
|
ELE15-02087
| Electrical Rough-In | 7/15/2015 | 7/16/2015 | 7/16/2015 9:18:22 AM | A | PASS |
|
|
Kevin Phone #: ###-#### grounding electrode and equipotential bond ok to pour slab
|