FIR14-00866
| INSP-Sprinkler Rough-in/Hydro | 7/16/2015 | 7/16/2015 | 7/16/2015 3:22:22 PM | P | PASS |
|
|
Hydrostatic pressure test of all the wet pipe systems for the above parking garage areas, including each floor of the residential building, and the clubhouse. (5 total wet systems). All tested at 200 psi @ 2hrs - All passed.
|
FIR14-00628
| INSP-Sprinkler Rough-in/Hydro | 7/16/2015 | 7/16/2015 | 7/16/2015 11:37:34 AM | P | PASS |
|
|
Hydrotest (200 psi @ 2hrs.) of dry pipe system protecting parking garage level. PASSED
|
FIR14-00866
| INSP-Sprinkler Rough-in/Hydro | 7/15/2015 | 7/16/2015 | 7/16/2015 11:35:35 AM | A | CANC |
|
|
Wrong permit # called in for this inspection - See permit FIR 14-00628 for inspection/test conducted this visit.
|