Inspections for the day of: Monday, July 17, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02394 FIRE-Conference7/17/20067/17/20067/17/2006 4:56:10 PMPDONE
Dan and I went over inspection procedure for the sprinkler system above the special ceiling.
BLD06-00538 FIRE-Final Inspection7/14/20067/17/20067/17/2006 3:54:42 PMPCANC
val; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR06-00473 INSP-Final Inspection7/17/20067/17/20067/17/2006 3:33:08 PMPPASS
permit finaled
BLD06-00241 FIRE-Final Inspection7/17/20067/17/20067/17/2006 3:31:40 PMPFAIL
Need the fire sprinkler permit finaled. No approved fire sprinkler drawings on site for an impromptu inspection. Fire life safety ok to final when sprinklers are done.
FIR06-00407 INSP-Sprinkler Rough-in7/17/20067/17/20067/17/2006 12:50:37 PMPPASS
Sprinkler piping as marked on the plans located over the hardlid areas on the west half of the first floor are ok to cover.
BLD04-02738 FIRE-Final Inspection7/14/20067/17/20067/17/2006 11:05:45 AMAFAIL
Provide city approved plans and notes. Also the fire extinguishers are mounted too high, the doors require spring hinges and smoke detectors are required in the first floor egress corridor from the bedrooms. This was only a partial inspection since there were no plans.
BLD04-02740 FIRE-Final Inspection7/14/20067/17/20067/17/2006 11:05:32 AMAFAIL
Provide city approved plans and notes. Also the fire extinguishers are mounted too high, the doors require spring hinges and smoke detectors are required in the first floor egress corridor from the bedrooms. This was only a partial inspection since there were no plans.
BLD06-00537 FIRE-Final Inspection7/14/20067/17/20067/17/2006 9:23:49 AMAFAIL
Provide drawings/notes for the shell permit BLD06-00379so that it can be finaled. Provide landings at the exits. Repair exit signs and provide emergency lighting as per the approved plans.
FIR06-00219 INSP-Final Inspection7/14/20067/17/20067/17/2006 8:18:34 AMACANC
Contact: Chris; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley