Inspections for the day of: Tuesday, July 17, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00584 INSP-Conference7/16/20077/17/20077/17/2007 1:29:22 PMADONE
On site visit, discussed with contractor the requirement for the installation to comply with NFPA 13 2002, specifically 12.1.5 (1) regarding sprinkler protection per design for the more demanding area shall extend a min. of 15 ft. beyond its perimeter.
BLD07-01656 FIRE-Final Inspection7/17/20077/17/20077/17/2007 1:22:28 PMPCANC
Inspection rescheduled.
BLD07-01656 FIRE-Final Inspection7/17/20077/17/20077/17/2007 1:15:37 PMPDEFR
phil - fire life safety Phone #: ###-####
FIR07-00448 INSP-Sprinkler Rough-in/Hydro7/17/20077/17/20077/17/2007 12:29:31 PMPDEFR
Scheduled 7/18
FIR07-00436 INSP-Alarm Testing7/16/20077/17/20077/17/2007 12:26:55 PMPNR
Pending shell and core fire alarm permit final.
FIR07-00435 INSP-Alarm Testing7/16/20077/17/20077/17/2007 12:25:55 PMPNR
Need the shell and core fire alarm permit finaled prior to tenant FA final.
FIR07-00244 INSP-Sprinkler Rough-in7/17/20077/17/20077/17/2007 12:24:17 PMPPART
Items on c/n verified for compliance, OH rough-in is approved for cover at the drop ceilings.
BLD07-00343 FIRE-Final Inspection7/17/20077/17/20077/17/2007 12:22:33 PMPPASS
Corrections are finished, fire life safety inspection passed.
FIR07-00193 INSP-Final Inspection7/17/20077/17/20077/17/2007 12:21:37 PMPPASS
Required correction verified for completion, fire sprinkler permit finaled.
FIR07-00127 INSP-Final Inspection7/11/20077/17/20077/17/2007 12:20:33 PMAPASS
Fire alarm permit finaled.
BLD07-00739 FIRE-Final Inspection7/16/20077/17/20077/17/2007 12:00:00 AMACANC
eva Phone #: ###-#### cancelled