ESC07-00787
| General Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 3:52:13 PM | P | PASS |
|
|
looked ok
|
ESC08-00336
| General Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 3:50:36 PM | P | PASS |
|
|
looked ok
|
ESC08-00439
| General Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 3:49:37 PM | P | PASS |
|
|
looked ok
|
ESC08-00578
| General Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 3:48:46 PM | P | PASS |
|
|
looked ok
|
ELE08-00106
| Final | 7/17/2008 | 7/17/2008 | 7/17/2008 3:47:22 PM | P | PASS |
|
|
dan Note: call dan for access Phone #: ###-#### ok to final, left survey, NEC 422.11(A) a/c branch corcuit shall be protected according to marked nameplate
|
ELE08-01787
| Electrical Rough-In | 7/16/2008 | 7/17/2008 | 7/17/2008 3:02:26 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/16/2008 at 9:47:22 PM. Contact: ###-####. called, left message, left correction notice, NEC 330.30 mc cable shall be secured within 12" of box, 330.17 mc cable shall be protected in accordance with 300.4(A), (C), & (D) where installed through framing members (1/14"), BCC mc cable shall not be run in valley of steel studs
|
ELE08-01976
| Permanent Service | 7/17/2008 | 7/17/2008 | 7/17/2008 2:15:40 PM | P | FAIL |
|
|
ray Phone #: ###-#### called, left correction notice, NEC 250.24 gec shall not splice thru enclosure, but be connected directly to each service point
|
ELE08-01976
| Electrical Rough-In | 7/17/2008 | 7/17/2008 | 7/17/2008 1:31:12 PM | P | FAIL |
|
|
ray Phone #: ###-#### called, left correction notice, 110.14(A) terminal connections shall ensure a thoroughly good connection (garage), 334.30 nm cable shall not be stapled on edge, and be secured within 12" of panel, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing member, 210.52 (A)(1) receptacles shall be installed such that no point along floor line is over 6' from a receptacle outlet (upper bedroom, nw )
|
ELE08-01650
| Electrical Rough-In | 7/17/2008 | 7/17/2008 | 7/17/2008 12:45:08 PM | P | PART |
|
|
underground - contact is Toby Groves ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis central west u/g south of school ok to cover
|
ELE07-03153
| Final | 7/16/2008 | 7/17/2008 | 7/17/2008 10:11:31 AM | A | PASS |
|
|
John- call 30 min prior to going Phone #: ###-#### ok to final
|
ELE06-02073
| Conference | 7/16/2008 | 7/17/2008 | 7/17/2008 9:49:16 AM | A | DONE |
|
|
brian Phone #: ###-#### looked at progression of construction, told owner to call for ri inspection, looked at plans, told what we would need to look at
|
ELE08-01312
| Final | 7/16/2008 | 7/17/2008 | 7/17/2008 9:08:19 AM | A | NH |
|
|
Homeowners are supposed to be home till 10. Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called, left message, left card, fee due, no esc this project
|
ELE08-01967
| Conference | 7/16/2008 | 7/17/2008 | 7/17/2008 8:39:22 AM | A | DONE |
|
|
Jim is the contact his cell number is ###-####. Phone #: ###-#### Internet Inspection Request from: Shawna Gates talked about mc cable in chase with low voltage to point of sale for about 20',said had to ground chase, no esc this project
|
ELE08-01029
| Electrical Rough-In | 7/16/2008 | 7/17/2008 | 7/17/2008 8:16:07 AM | A | CANC |
|
|
Bud- ceiling Phone #: ###-#### wrong type inspection, see part final
|
ELE08-01029
| Final | 7/17/2008 | 7/17/2008 | 7/17/2008 8:15:53 AM | A | PART |
|
|
Bud- ceiling Phone #: ###-#### ok to part final ceiling anop
|