BLD08-01402
| FIRE-Final Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 4:30:08 PM | P | PASS |
|
|
Life safety passed
|
BLD08-00715
| FIRE-Final Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 2:34:04 PM | P | FAIL |
|
|
Provide approved hardware on the two north facing exit doors, provide two mounted and tagged fire extinguishers and provide verification that the new hvac units do not require automatic shutdown as per IMC
|
FIR08-00036
| INSP-Sprinkler Rough-in/Hydro | 7/16/2008 | 7/17/2008 | 7/17/2008 2:24:32 PM | P | PASS |
|
|
The underground hydro test passed and the underground flush passed.
|
BLD08-01383
| FIRE-Final Inspection | 7/16/2008 | 7/17/2008 | 7/17/2008 1:52:53 PM | P | CANC |
|
|
The project related fire sprinkler permit did not get called in for inspection.
|
BLD08-00802
| FIRE-Final Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 1:48:19 PM | P | PASS |
|
|
life safety passed.
|
BLD08-00764
| FIRE-Final Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 10:55:17 AM | P | FAIL |
|
|
Mount the fire extinguisher in a normal path of travel and provide with a current inspection tag. Repair the combination exit sign/emergency light located over the exit door.
|
BLD08-00763
| FIRE-Final Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 10:53:38 AM | P | CANC |
|
|
The tenant space was not ready for an inspection. Contractor is going to reschedule.
|
FIR08-00481
| INSP-Final Inspection | 7/17/2008 | 7/17/2008 | 7/17/2008 10:11:01 AM | P | PASS |
|
|
Permit finaled
|