Inspections for the day of: Friday, July 17, 2009.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01154 FIRE-Final Inspection7/17/20097/17/20097/17/2009 4:11:48 PMPPASS
Life safety passed. The lighting in the stairwell is complete and the north exit sign has been repaired.
BLD09-00427 FIRE-Conference7/17/20097/17/20097/17/2009 4:10:54 PMPDONE
I went over the gas cabinet requirements with Greg. He is limited to 504 cubic feet as per fire review note #12.
FIR09-00399 INSP-Sprinkler Rough-in/Hydro7/17/20097/17/20097/17/2009 2:25:48 PMPPASS
Rough-in passed. Piping can be covered.
FIR09-00366 INSP-Sprinkler Rough-in/Hydro7/17/20097/17/20097/17/2009 2:15:53 PMPPASS
The piping can be covered. Not all of the wall and ceiling supports had been installed so actual pendant spacing could not be verified. Hangers and pipe sizing was ok.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/10/20097/17/20097/17/2009 2:12:14 PMACANC
Cancelled due to time constraints.
BLD06-01451 FIRE-Final Inspection7/16/20097/17/20097/17/2009 2:11:33 PMACANC
Rescheduled for monday as per Zac
BLD09-00566 FIRE-Final Inspection7/16/20097/17/20097/17/2009 10:22:04 AMAPASS
life safety passed
FIR09-00339 INSP-Final Inspection7/17/20097/17/20097/17/2009 10:21:07 AMPPASS
Permit finaled.
FIR08-00441 INSP-Final Inspection7/16/20097/17/20097/17/2009 10:04:48 AMAFAIL
Sprinklers are blocked by light fixtures in mechanical room and master closet.
FIR09-00291 INSP-Final Inspection7/17/20097/17/20097/17/2009 9:41:59 AMPCANC
Randy Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
FIR09-00412 INSP-Final Inspection7/16/20097/17/20097/17/2009 9:23:35 AMAPASS
permit finaled
FIR09-00419 INSP-Sprinkler Rough-in7/16/20097/17/20097/17/2009 9:17:34 AMAFAIL
The new 6" underground supply piping does not meet the state requirement of a minumum 4'-6" bury depth. I went over the depth of bury with EKC while on site and contacted Trent with Phoenix Fire. Pipe can not be buried until re-inspected.
FIR09-00244 INSP-Final Inspection7/16/20097/17/20097/16/2009 12:58:17 PMAPASS
Permit finaled
FIR09-00377 INSP-Final Inspection7/16/20097/17/20097/16/2009 12:57:31 PMAPASS
Permit finaled