BLD04-01154
| FIRE-Final Inspection | 7/17/2009 | 7/17/2009 | 7/17/2009 4:11:48 PM | P | PASS |
|
|
Life safety passed. The lighting in the stairwell is complete and the north exit sign has been repaired.
|
BLD09-00427
| FIRE-Conference | 7/17/2009 | 7/17/2009 | 7/17/2009 4:10:54 PM | P | DONE |
|
|
I went over the gas cabinet requirements with Greg. He is limited to 504 cubic feet as per fire review note #12.
|
FIR09-00399
| INSP-Sprinkler Rough-in/Hydro | 7/17/2009 | 7/17/2009 | 7/17/2009 2:25:48 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR09-00366
| INSP-Sprinkler Rough-in/Hydro | 7/17/2009 | 7/17/2009 | 7/17/2009 2:15:53 PM | P | PASS |
|
|
The piping can be covered. Not all of the wall and ceiling supports had been installed so actual pendant spacing could not be verified. Hangers and pipe sizing was ok.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 7/10/2009 | 7/17/2009 | 7/17/2009 2:12:14 PM | A | CANC |
|
|
Cancelled due to time constraints.
|
BLD06-01451
| FIRE-Final Inspection | 7/16/2009 | 7/17/2009 | 7/17/2009 2:11:33 PM | A | CANC |
|
|
Rescheduled for monday as per Zac
|
BLD09-00566
| FIRE-Final Inspection | 7/16/2009 | 7/17/2009 | 7/17/2009 10:22:04 AM | A | PASS |
|
|
life safety passed
|
FIR09-00339
| INSP-Final Inspection | 7/17/2009 | 7/17/2009 | 7/17/2009 10:21:07 AM | P | PASS |
|
|
Permit finaled.
|
FIR08-00441
| INSP-Final Inspection | 7/16/2009 | 7/17/2009 | 7/17/2009 10:04:48 AM | A | FAIL |
|
|
Sprinklers are blocked by light fixtures in mechanical room and master closet.
|
FIR09-00291
| INSP-Final Inspection | 7/17/2009 | 7/17/2009 | 7/17/2009 9:41:59 AM | P | CANC |
|
|
Randy Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
|
FIR09-00412
| INSP-Final Inspection | 7/16/2009 | 7/17/2009 | 7/17/2009 9:23:35 AM | A | PASS |
|
|
permit finaled
|
FIR09-00419
| INSP-Sprinkler Rough-in | 7/16/2009 | 7/17/2009 | 7/17/2009 9:17:34 AM | A | FAIL |
|
|
The new 6" underground supply piping does not meet the state requirement of a minumum 4'-6" bury depth. I went over the depth of bury with EKC while on site and contacted Trent with Phoenix Fire. Pipe can not be buried until re-inspected.
|
FIR09-00244
| INSP-Final Inspection | 7/16/2009 | 7/17/2009 | 7/16/2009 12:58:17 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00377
| INSP-Final Inspection | 7/16/2009 | 7/17/2009 | 7/16/2009 12:57:31 PM | A | PASS |
|
|
Permit finaled
|