Inspections for the day of: Friday, July 17, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00850 INSP-Final Inspection7/16/20157/17/20157/17/2015 3:48:23 PMPPASS
Inspection of fire alarm inteface with fire sprinkler systems (dry and wet) including waterflows, tampers, low-air alarm for dry system, and a trip test of the dry pipe valve. Also tested audibility throughout the building during these tests to ensure adequate alarm audibility and intelligentability (voice evac system). All devices tested OK, except the trip test of the dry pipe valve, that will require further work. No other initiating devices tested this visit. Elevators also not tested.
For next inspection, will try to complete fire sprinkler systems, elevators, doors on hold-open and SDs to activate, SFDs, etc.
FIR14-00866 INSP-Final Inspection7/16/20157/17/20157/17/2015 3:43:52 PMPPART
Test/inspection of all fire sprinkler systems (dry and wet) and interface with fire alarm system, including tampers, waterflows, low-air f/ dry system, sectional control valves, and a trip test of the dry pipe valve protecting the parking garage.
All devices tested OK and within time requirements, except the dry pipe valve that only delivered water within 90 seconds trip test. Therefore an accelerator device will be required on this system to get below the 60 second time requirement.
FIR14-00708 INSP-Sprinkler Rough-in7/16/20157/17/20157/17/2015 12:34:33 PMAPART
RTC wet // Bldg. E - 1st floor, Bldg. F - 2nd, 3rd and 4th floor hard lid corridors and comon rooms off the corridors.
NOTE: 4th floor Bldg F had some rooms that were already covered, so could not inspect these areas. Some sheetrock in these rooms will have to be removed to complete inspection of these rooms. See plans for areas inspected and OK to cover for this visit.
FIR14-00687 INSP-Sprinkler Rough-in7/15/20157/17/20157/17/2015 12:31:07 PMAPART
RTC inspection for first floor wet-pipe system protecting the office area - hard lid areas.
OK to cover pipe in this area.