Inspections for the day of: Monday, July 17, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02179 ELE-Aging Inspection7/17/20177/17/20177/19/2017 9:37:35 AM DONE
Talked with a person and he will look into, job has 2 permits on it
ELE09-01607 ELE-Aging Inspection7/17/20177/17/20177/19/2017 9:36:29 AM FAIL
Stopped by and left a correction notice to call for a conference on 7/19/2017
ELE16-01134 Electrical Rough-In7/17/20177/17/20177/17/2017 2:18:32 PMPPASS
We are requesting a rough-in inspection on level 6 ; 8 the king rooms, level 3 Pool corridor ceilings and the elevator lobby ceiling on level 9 ; 10. Our contact is Nic @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate
Areas as noted on inspection request ok cover
ELE17-02217 Electrical Rough-In7/14/20177/17/20177/17/2017 1:35:06 PMPNR
Chris Phone #: ###-####
Not ready
ELE17-02198 Electrical Rough-In7/14/20177/17/20177/17/2017 9:58:43 AMAPASS
underground for spa Phone #: ###-#### Inspection requested via web by Louis Keller
Underground for pool being fed from future shop ok cover
ELE15-03035 Final7/14/20177/17/20177/17/2017 9:57:10 AMAFAIL
Call Paul if you have questions ###-####. thank you Phone #: ###-#### Inspection requested via web by Steve Blackmer
406.4 (d)(5) tamper resistant receptacles required(kitchen backsplash)
110.25 lockable disc for dishwasher and hood
406.6 faceplates needed for up 3-gang in master bed
110.7 stubs in up bath need safe ended,outlets in up storage and patio need trimmed out, outlet up landing by chimney pipe in-op
4-05-23 unlawful to conceal any electrical installations up floor heat was installed by tile guy and was never looked at. Need number of this individual or electrical contractor needs to assume resposibility of product and protection of floor heat.
ELE17-02251 Electrical Rough-In7/14/20177/17/20177/17/2017 8:20:43 AMAPASS
Walls Only Phone #: ###-#### Inspection requested via web by Dean Gernaat
Walls only ok cover
ELE17-02143 Rough-In Permanent Service7/14/20177/17/20177/16/2017 6:03:05 PMPCANC
Please call me 20 minutes before hand so I can meet you at the house. Thank you. Phone #: ###-#### >> Inspection requested via web by Anthony Bongiovano Inspection cancelled from web by: Anthony Bongiovano