ELE18-02234
| Electrical Rough-In | 7/17/2018 | 7/17/2018 | 7/17/2018 3:44:58 PM | P | PART |
|
|
Correction for fire makeup pump not required for 1 and 2 family dwellings. Nail plates still required, recall when ready. Ok to foam seal
|
ELE18-02683
| Electrical Rough-In | 7/17/2018 | 7/17/2018 | 7/17/2018 2:06:59 PM | P | FAIL |
|
|
Call Corbin with any technical questions ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg 210.11- Bathroom receptacles shall be on a dedcated 20 amp circuit. * Wiring incomplete in kitchen and ceilings. Wiring hanging from ceilings and walls, empty boxes in kitchen.
|
ELE18-02678
| Electrical Rough-In | 7/17/2018 | 7/17/2018 | 7/17/2018 1:35:01 PM | P | PASS |
|
|
remodle Phone #: ###-#### Inspection requested via web by cal crosby Basement walls not opened up. New wiring upstairs and main level rough in ok cover
|
ELE18-02674
| Electrical Rough-In | 7/16/2018 | 7/17/2018 | 7/17/2018 12:45:29 PM | A | PASS |
|
|
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt Rough in ok cover
|
ELE18-02234
| Electrical Rough-In | 7/16/2018 | 7/17/2018 | 7/17/2018 12:44:49 PM | A | FAIL |
|
|
this is for rough-in only. Service will be installed in next couple of weeks. please call Bill with any ? Phone #: ###-#### Inspection requested via web by Bob Glenn 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. several thru out. 695.6- Feeders to fire pump shall be protected from damage either from encasement in concrete or pire resistant cable.
|
ELE18-02672
| Electrical Rough-In | 7/16/2018 | 7/17/2018 | 7/17/2018 10:09:57 AM | A | PASS |
|
|
New office wall cover Outlets on existing wall fished in. Contact Lance for door access if job is locked up. Phone #: ###-#### Inspection requested via web by David Feller Wall rough in ok cover
|
ELE18-02675
| Electrical Rough-In | 7/16/2018 | 7/17/2018 | 7/17/2018 9:35:10 AM | A | PASS |
|
|
rough in walls for cover Phone #: ###-#### Inspection requested via web by Ron Zimmerman 90 percent of walls 1 sided with drywall. Informed any additional cover prior to inspection will result in red tag and removal of cover will be mandatory. Wall rough in ok cover
|
ELE18-01590
| Rough-In Permanent Service | 7/16/2018 | 7/17/2018 | 7/17/2018 8:54:38 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Rough in ok cover p/s u/g n ok
|