Inspections for the day of: Tuesday, July 17, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01381 Final7/17/20187/17/20187/17/2018 3:57:50 PMPCANC
rescheduled to next day
ELE18-00397 Permanent Service7/17/20187/17/20187/17/2018 3:06:24 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins...p/s u/g new ok
ELE18-02531 Electrical Rough-In7/17/20187/17/20187/17/2018 2:34:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake...rough ok to cover..service grounding brought up to code and using existing panel...pushmatic panel previously oked by Daryl Degrange...back seperate building has seperate address 6616 and has nothing do to with this project
ELE18-02563 Electrical Rough-In7/17/20187/17/20187/17/2018 2:02:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Burke...ok to cover rough in minus back patio and fireplace...rough in inspection needs scheduled once built and installed
ELE18-02686 Electrical Rough-In7/17/20187/17/20187/17/2018 1:19:13 PMPPASS
New covered back patio Phone #: ###-#### Inspection requested via web by danny perrine...ok to cover...outlets and exterior lighting cut in once sided
ELE18-00083 Final7/17/20187/17/20187/17/2018 1:03:18 PMPPASS
inspection scheduled to final out permit...contractor was responsible for rough in only...trim out and connection to panels done by other electrical contractor and takes responsibility for work
ELE18-01381 Final7/16/20187/17/20187/17/2018 1:00:41 PMACANC
Phone #: ###-#### Inspection requested via web by Troy Cobb...rescheduled to PM so can repair some violations
ELE18-02138 Final7/16/20187/17/20187/17/2018 11:14:16 AMAFAIL
Phone #: ###-#### Inspection requested via web by BRS Permitting...no access...under age child only one home...adult or representative shall be present for inspection
ELE18-02364 Electrical Rough-In7/15/20187/17/20187/17/2018 10:46:33 AMAPASS
Please call 15 minutes before arrival. Thanks. Phone #: ###-#### Inspection requested via web by Robert Pietras...rated fan boxes and remodel cans be used...boxes cut in for switching...ok to cover patio ceiling
ELE18-00069 Electrical Rough-In7/16/20187/17/20187/17/2018 10:28:20 AMACANC
Bill Phone #: ###-####...converted to conference
ELE18-00069 Conference7/17/20187/17/20187/17/2018 10:27:57 AMAPASS
Bill Phone #: ###-####...discussed stapling of wires, box fill/sizing, makeup of wires, bathroom outlet circuit requirement, ARC fault protection, and junction box access and blanking
ELE18-00849 Conference7/17/20187/17/20187/17/2018 9:35:29 AMAPASS
plenum wall discussion...met with plumbing, hvac, general of job, and electrical foreman and discussed wiring of walls being used as plenum....confusion on prints how walls being used...return or supply of air in manufactureing plant area
ELE17-02649 Final7/16/20187/17/20187/17/2018 8:53:45 AMAPART
This is a partial final - for roof. Contact is Andy Chambers. Phone #: ###-#### Inspection requested via web by Scott Campbell...roof top units ok