Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00089 INSP-Sprinkler Rough-in7/18/20057/18/20057/18/2005 4:17:22 PMPFAIL
Contractor could not produce approved plans for review on site. Noted some deficiencies including missing EQ bracing, missing retaining straps, and sprig-ups with ssu heads in the pendent position.
BLD05-00687 FIRE-Final Inspection7/18/20057/18/20057/18/2005 2:27:40 PMPPASS
Fire life safety passed inspection.
BLD04-02157 FIRE-Final Inspection7/18/20057/18/20057/18/2005 2:10:40 PMPFAIL
Provide sign at main entry/exit door stating "This door to remain unlocked while building is occupied", mount provided fire ext. along a normal path of travel with the handle no higher than 48" AFF, verify fire sprinkler system is current with an annual inspection.
BLD05-00687 FIRE-Final Inspection7/15/20057/18/20057/18/2005 11:14:30 AMAFAIL
Provide building address, install fire ext. within a normal path of travel, verify function of emergency discharge lighting.
BLD05-00568 FIRE-Final Inspection7/15/20057/18/20057/18/2005 11:11:13 AMAPASS
Fire life safety finaled.
BLD04-01429 FIRE-Final Inspection7/18/20057/18/20057/18/2005 11:09:33 AMPPASS
Fire life safety passed inspection.
BLD04-02481 FIRE-Final Inspection7/15/20057/18/20057/18/2005 9:59:40 AMAFAIL
Provide one 2A10BC fire ext. per level with current inspection tag, provide lever hardware and remove thumbturns at both main entry/exit and back doors as discussed and required per note #4 on fire review comments, remove two doors at kittchen area, no storage allowed in attic space per note #2 on plan review report.
BLD05-01429 FIRE-Final Inspection7/15/20057/18/20057/18/2005 9:10:15 AMACANC
Cancel inspection, permit number and address do not correspond.
BLD05-00316 FIRE-Final Inspection7/18/20057/18/20057/18/2005 12:00:00 AMPPASS
Fire life safety finaled.