Inspections for the day of: Tuesday, July 18, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00328 INSP-Sprinkler Rough-in7/17/20067/18/20067/18/2006 2:32:04 PMPPASS
The sprinkler piping as marked on the plans that is located above the ceilings is ok to cover.
MIS06-00176 FIR-Final7/14/20067/18/20067/18/2006 1:58:33 PMPPART
A temporary occupancy was given until the emergency light is repaired or removed, the locking hardware on the storage room door is removed and the fire extinguisher is about to expire.
BLD05-02671 FIRE-Final Inspection7/17/20067/18/20067/18/2006 12:44:05 PMAPASS
life safety finaled
BLD06-00537 FIRE-Final Inspection7/17/20067/18/20067/18/2006 10:50:46 AMAPASS
Life safety finaled
BLD06-00379 FIRE-Final Inspection7/17/20067/18/20067/18/2006 10:49:01 AMAPASS
Life safety finaled. Water supply documentation was provided to me. Per IFC appendix B table 2,250 gallons are required. Per the documentation from United Water 2,250 is what is available.
FIR06-00176 FIR-Aging Inspection7/18/20067/18/20067/18/2006 10:14:54 AM NR
work is in progress