ELE07-02528
| Conference | 7/18/2007 | 7/18/2007 | 7/18/2007 3:58:46 PM | P | DONE |
|
|
ed- ###-####-- talked about box fill and circuits for enclosed room over exst slab and when to call for inspection, free conductor length, new ckts and recpt spacing
|
ELE07-02524
| Electrical Rough-In | 7/17/2007 | 7/18/2007 | 7/18/2007 3:39:45 PM | P | PASS |
|
|
wayne - underground; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang u/g east side bldg only ok to cover
|
ELE07-02415
| Electrical Rough-In | 7/18/2007 | 7/18/2007 | 7/18/2007 2:52:44 PM | P | PASS |
|
|
clyde; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, ok to cover ceiling
|
ELE06-04004
| Final | 7/17/2007 | 7/18/2007 | 7/18/2007 2:03:05 PM | P | FAIL |
|
|
1:00 please...Duane ###-#### met owner, left correction notice, told owner he has to have contractor permit and final installation, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be strapped within 8" of box, 312.5 all conductors entering enclosure shall have abrasion protection, 250.53(B)&(G) electrodes shall be minimum 6' apart and driven in flush with or below grade, 406.8(B) outside recpts shall have enclosure that is weatherproof whether or not plug is inserted, 300.14 shall provide minimum 6" free length conductor at each box, 110.3(B) listed equipment shall be installed per instruction included with with listing (tighten clamps), BCC must update permit for service request
|
ELE07-02506
| Electrical Rough-In | 7/18/2007 | 7/18/2007 | 7/18/2007 12:57:38 PM | P | PASS |
|
|
We have made the changes in the bathroom that Pat requested by useing Colorado Jim straps Phone #: ###-#### Internet Inspection Request from: Scott Abbott corrections made, ric walls only ok plus hard lids in baths
|
ELE07-02534
| Conference | 7/18/2007 | 7/18/2007 | 7/18/2007 12:21:18 PM | P | DONE |
|
|
Kong ###-#### talked about wiring for covered patio, ri and final, recpts to be above panel in clg
|
ELE07-02349
| Permanent Service | 7/17/2007 | 7/18/2007 | 7/18/2007 10:53:47 AM | A | PASS |
|
|
calvin; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr made, p/s o/h n ok
|
ELE07-01059
| ELE-Aging Inspection | 7/18/2007 | 7/18/2007 | 7/18/2007 10:19:17 AM | | DONE |
|
|
see final
|
ELE07-01059
| Final | 7/18/2007 | 7/18/2007 | 7/18/2007 10:19:02 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE07-01197
| ELE-Aging Inspection | 7/18/2007 | 7/18/2007 | 7/18/2007 9:50:30 AM | | DONE |
|
|
see final
|
ELE07-01197
| Final | 7/18/2007 | 7/18/2007 | 7/18/2007 9:50:18 AM | A | PASS |
|
|
looked at signs, ok to final
|
ELE07-00860
| Final | 7/18/2007 | 7/18/2007 | 7/18/2007 9:41:41 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE07-02478
| Electrical Rough-In | 7/17/2007 | 7/18/2007 | 7/18/2007 9:03:45 AM | A | PASS |
|
|
FLOOR BOX RI Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ok to pour 2 floor boxes only
|
ELE07-01362
| Final | 7/17/2007 | 7/18/2007 | 7/18/2007 8:36:40 AM | A | PASS |
|
|
Thanks Jack!! Phone #: ###-#### Internet Inspection Request from: Tracy corr made, ok to final, signed occ card
|