Inspections for the day of: Friday, July 18, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01408 ELE-Aging Inspection7/18/20087/18/20087/18/2008 4:03:12 PM FAIL
no work being done on this project
ELE07-01407 ELE-Aging Inspection7/18/20087/18/20087/18/2008 3:54:26 PM FAIL
no work being done on this project
ELE06-04442 DOC - Permit Expired7/18/20087/18/20087/18/2008 3:23:43 PMPPASS
no work being done on this project
ELE08-01890 Electrical Rough-In7/18/20087/18/20087/18/2008 3:04:07 PMPPASS
Scheduled by a contractor via Hello! on 7/18/2008 at 9:36:27 AM. Contact: ###-####.
ELE08-01890 Permanent Service7/18/20087/18/20087/18/2008 3:03:54 PMPPASS
Scheduled by a contractor via Hello! on 7/18/2008 at 9:36:27 AM. Contact: ###-####.
P/S U/G N Ok
ELE08-01995 Electrical Rough-In7/18/20087/18/20087/18/2008 2:17:38 PMPPASS
Kevin- call 30 min prior to access Phone #: ###-####
no esc R/I Ok
ELE08-01611 Electrical Rough-In7/17/20087/18/20087/18/2008 1:45:09 PMPPASS
bruce Phone #: ###-####
ceiling ok for cover
ELE08-01971 Permanent Service7/17/20087/18/20087/18/2008 12:48:44 PMAPASS
This Qwest pedestal project IS complete now and ready for permanent service. Thanks. Phone #: ###-#### Internet Inspection Request from: Clint Tate
no esc in project
P/S U/G N Ok
ELE08-01971 DOC - Permit Finaled7/18/20087/18/20087/18/2008 12:48:06 PMPPASS
ELE07-03307 Electrical Rough-In7/17/20087/18/20087/18/2008 11:51:00 AMAPART
Contact: Neil Ramsey - rough in inspection, 1st floor exit stairwells both East and West please Phone #: ###-#### Internet Inspection Request from: Deb Gooden
1st floor exit stairwells both East and West ok
ELE08-01046 Final7/18/20087/18/20087/18/2008 11:04:51 AMAPASS
Scheduled by a contractor via Hello! on 7/18/2008 at 6:38:10 AM. Contact: ###-####.
ELE07-03352 Final7/18/20087/18/20087/18/2008 11:04:38 AMAPASS
Scheduled by a contractor via Hello! on 7/18/2008 at 6:39:56 AM. Contact: ###-####.
ELE08-01509 Final7/17/20087/18/20087/18/2008 10:08:55 AMANR
We need finals for store fronts at suites 182 & 184, Thank you Phone #: ###-#### Internet Inspection Request from: Lloyd Looney
call for final when finished I plug tested these two and that was ok but you had mc cable not terminated in a box and pipes not strraped also another permit must be taken out for each of these prior to occupancy on a t/i permit.
ELE08-01749 Rough-In Permanent Service7/18/20087/18/20087/18/2008 9:44:29 AMAPASS
Scheduled by a contractor via Hello! on 7/18/2008 at 7:28:30 AM. Contact: ###-####.
no esc in project
R/I Ok
P/S U/g N Ok
ELE08-01990 Electrical Rough-In7/17/20087/18/20087/18/2008 9:00:32 AMAPART
Dave Shifflett Phone #: ###-#### Internet Inspection Request from: jason shifflett no esc in project
ok to cover check for 4 sq. metal boxes on service inspection nm boxes not permited with mc cable and riser used for support must be 2 in imc
ELE08-01926 Electrical Rough-In7/16/20087/18/20087/18/2008 8:57:07 AMAPASS
Ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten
no esc in project
ELE08-01926 DOC - Permit Finaled7/18/20087/18/20087/18/2008 8:56:46 AMPPASS