FIR07-01012
| INSP-Alarm Testing | 7/18/2008 | 7/18/2008 | 7/18/2008 5:45:21 PM | P | DEFR |
|
|
wip
|
BLD07-00133
| FIRE-Final Inspection | 7/18/2008 | 7/18/2008 | 7/18/2008 5:44:20 PM | P | PASS |
|
|
Fire life safety passed.
|
BLD08-01504
| FIRE-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 5:42:58 PM | A | PASS |
|
|
Life safety completed satisfactory.
|
BLD08-01286
| FIRE-Final Inspection | 7/18/2008 | 7/18/2008 | 7/18/2008 5:42:07 PM | A | PASS |
|
|
Vanilla permit life safety inspection passed.
|
FIR08-00360
| INSP-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 1:45:34 PM | A | PART |
|
|
Revised head locations at the tenant improvement area are acceptable, circled one head above an office ceiling that will need to be relocated or capped (flex head whip is currently attatched to a ceiling tile pushed above the grid), also need to verify correct coverage outside the new wall locations.
|
FIR08-00068
| INSP-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 1:38:46 PM | A | FAIL |
|
|
See annotations on stamped plan set for locations in need of repair including one painted upright head, one pendent blocked by an adjacent light fixture at the women's locker room, one missing escutcheon, two heads blocked by insulation at the ceiling in the OTS storage room.
|
FIR08-00066
| INSP-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 1:35:39 PM | A | PART |
|
|
Need to provide matched temperature heads at the east mechanical room. Remainder of fire sprinkler work is acceptable and okay for final once correction is made.
|
BLD07-03026
| FIRE-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 1:32:44 PM | A | FAIL |
|
|
Provide building address, provide approved hardware at both sets of horizontal slider exit doors per review notes, repair one EM light and install one missing EM light, also need to complete project related fire sprinkler permit correction notice prior to final life safety approval.
|
BLD07-03027
| FIRE-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 1:29:43 PM | A | FAIL |
|
|
Provide approved hardware at the horizontal slider exit doors, repair one EM light at the west hall, provide signage at the fire extinguisher cabinets, need project related fire sprinkler permit finaled.
|
BLD07-02653
| FIRE-Final Inspection | 7/17/2008 | 7/18/2008 | 7/18/2008 9:54:11 AM | A | PASS |
|
|
Corrections okayed, fire life safety finaled.--ok per Forrest France for no Fire Alarm permit///7-23-08 BAS
|