Inspections for the day of: Friday, July 18, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01012 INSP-Alarm Testing7/18/20087/18/20087/18/2008 5:45:21 PMPDEFR
wip
BLD07-00133 FIRE-Final Inspection7/18/20087/18/20087/18/2008 5:44:20 PMPPASS
Fire life safety passed.
BLD08-01504 FIRE-Final Inspection7/17/20087/18/20087/18/2008 5:42:58 PMAPASS
Life safety completed satisfactory.
BLD08-01286 FIRE-Final Inspection7/18/20087/18/20087/18/2008 5:42:07 PMAPASS
Vanilla permit life safety inspection passed.
FIR08-00360 INSP-Final Inspection7/17/20087/18/20087/18/2008 1:45:34 PMAPART
Revised head locations at the tenant improvement area are acceptable, circled one head above an office ceiling that will need to be relocated or capped (flex head whip is currently attatched to a ceiling tile pushed above the grid), also need to verify correct coverage outside the new wall locations.
FIR08-00068 INSP-Final Inspection7/17/20087/18/20087/18/2008 1:38:46 PMAFAIL
See annotations on stamped plan set for locations in need of repair including one painted upright head, one pendent blocked by an adjacent light fixture at the women's locker room, one missing escutcheon, two heads blocked by insulation at the ceiling in the OTS storage room.
FIR08-00066 INSP-Final Inspection7/17/20087/18/20087/18/2008 1:35:39 PMAPART
Need to provide matched temperature heads at the east mechanical room. Remainder of fire sprinkler work is acceptable and okay for final once correction is made.
BLD07-03026 FIRE-Final Inspection7/17/20087/18/20087/18/2008 1:32:44 PMAFAIL
Provide building address, provide approved hardware at both sets of horizontal slider exit doors per review notes, repair one EM light and install one missing EM light, also need to complete project related fire sprinkler permit correction notice prior to final life safety approval.
BLD07-03027 FIRE-Final Inspection7/17/20087/18/20087/18/2008 1:29:43 PMAFAIL
Provide approved hardware at the horizontal slider exit doors, repair one EM light at the west hall, provide signage at the fire extinguisher cabinets, need project related fire sprinkler permit finaled.
BLD07-02653 FIRE-Final Inspection7/17/20087/18/20087/18/2008 9:54:11 AMAPASS
Corrections okayed, fire life safety finaled.--ok per Forrest France for no Fire Alarm permit///7-23-08 BAS