Inspections for the day of: Monday, July 18, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00583 INSP-Sprinkler Rough-in/Hydro7/18/20117/18/20117/18/2011 3:57:45 PMPCANC
Request for a hydro for this afternoon was cancelled by Miguel when I arrived on site.
FIR11-00313 INSP-Final Inspection7/13/20117/18/20117/18/2011 3:56:08 PMAFAIL
Provide plan modifications showing the notification devices located on the correct circuits and the corrected candellas. Provide correct data sheets for the devices actually installed. The audible notification devices utilized a solid tone, not temporal. Research indicated that the fire alarm system was updated after the requirement for the temporal sound. Documentation needs to be provided indicating otherwise or the audible sound needs to be modified.
FIR11-00167 INSP-Sprinkler Rough-in/Hydro7/15/20117/18/20117/18/2011 11:58:53 AMAPASS
The above ground hydro test passed and the corrections have been made to the above ground piping. Piping can be covered.
FIR11-00269 INSP-Final Inspection7/15/20117/18/20117/18/2011 9:43:51 AMACANC
No inspection performed. To be rescheduled with the other project fire alarm permit.
FIR11-00319 INSP-Final Inspection7/15/20117/18/20117/18/2011 9:42:55 AMAFAIL
The inspection was stopped with no devices tested due to the fire alrm scope of work not matching the building permit scope of work. Also notification needs to be added in the Copy Room.