Inspections for the day of: Friday, July 18, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01304 ELE-Aging Inspection7/18/20147/18/20147/21/2014 2:37:27 PM DONE
Home owner still needs to complete smoke/ carbon detector installation
ELE14-01925 Final7/18/20147/18/20147/18/2014 2:01:45 PMPNR
Thanks. ###-#### Phone #: ###-#### >> Inspection requested via web by Clay Morgan Not ready for final at this time.
ELE14-01925 Permanent Service7/18/20147/18/20147/18/2014 2:01:00 PMPPASS
Thanks. ###-#### Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s o/h n ok
ELE14-01934 Electrical Rough-In7/18/20147/18/20147/18/2014 1:30:51 PMPPASS
Uffer ground inspection. Contact is Justin Bieker. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery rough-in ok cover concrete encased electrode
ELE14-01421 Final7/18/20147/18/20147/18/2014 1:12:58 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
ELE14-01948 Final7/17/20147/18/20147/18/2014 12:04:52 PMPNR
Contact: Jeremy Thornock. inspection for 2 ufer grounds Phone #: ###-#### >> Inspection requested via web by Deb Gooden Not ready for final at this time.
ELE14-01948 Electrical Rough-In7/18/20147/18/20147/18/2014 12:02:56 PMPPART
Contact: Jeremy Thornock. inspection for 2 ufer grounds Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rough-in ok cover 1 of 2 concrete encased electrodes, northwest corner
ELE14-01548 Electrical Rough-In7/18/20147/18/20147/18/2014 11:15:38 AMPPASS
Need 2nd grid ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Alan Lusk Rough-in ok cover ceiling grid in rms 102 thur 120
ELE14-01941 Rough-In Permanent Service7/17/20147/18/20147/18/2014 10:46:55 AMAFAIL
Call ahead for access, looking for 9:30ish inspection - Kevin Phone #: ###-#### Complete grounding connections NEC 230.6(5) shall not route unfused conductor along inside of walls of a building.
ELE14-01945 Final7/17/20147/18/20147/18/2014 9:06:08 AMAFAIL
Site is located near the southeast corner of the lot, next to N. Mitchell. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell see rough-in
ELE14-01945 Electrical Rough-In7/17/20147/18/20147/18/2014 9:05:17 AMAFAIL
Site is located near the southeast corner of the lot, next to N. Mitchell. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell NEC 406.8(B) All 15 and 20 ampere 120 and 250 volt receptacles shall be listed weather-resistant type.
ELE14-01925 Permanent Service7/17/20147/18/20147/18/2014 8:46:08 AMAFAIL
If you have any questions, please call Clay at ###-####. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan NEC 250.56 Permanent service requires two grounding electrodes. NEC 312.5(C) Prohitbits the installation of several cables bunched together. NEC 210.8 requires GFCI protection for all 15 and 20 ampere 120 volt receptacles.