Inspections for the day of: Monday, July 18, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00404 ELE-Aging Inspection7/18/20167/18/20167/19/2016 1:10:34 PM PASS
Still under construction
ELE16-02289 Final7/18/20167/18/20167/18/2016 3:57:55 PMPPASS
Power for ADA doors. Contact Travis Hust
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Final ok
ELE16-02231 Electrical Rough-In7/15/20167/18/20167/18/2016 3:56:52 PMAFAIL
Jason Phone #: ###-####
210.52- Receptacle outlets needed for wall spaces. Fixed panels of back slider are wall space and wall created by pocket door in office.
300.15- All NM cables shall terminate in a box. front patio light.
334.12- NM cable shall not be installed where subject to damage. Dining light switch leg stapled to wall surface.

Contractor called end of day, stubs under house for floor receptacles, front lights to be mounted when beam layout is decided, and bed S/L fixed. Will recall.
ELE16-02289 Electrical Rough-In7/18/20167/18/20167/18/2016 3:36:18 PMPPASS
Power for ADA doors. Contact Travis Hust
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
West entrance north set of doors only rough in ok.
ELE16-00151 Electrical Rough-In7/18/20167/18/20167/18/2016 3:34:10 PMPPASS
Wall rough in inspection for cover. Contact is Eric Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Basement north of concrete dividing wall rough in ok cover
ELE15-00495 Electrical Rough-In7/18/20167/18/20167/18/2016 3:19:57 PMPPASS
Can light ceiling inspection for cover high ceiling at column line A and B breeze way. Contact is Eric Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Breezeway lid complete rough in ok cover
ELE16-02290 Electrical Rough-In7/18/20167/18/20167/18/2016 2:46:59 PMPPASS
Contact/Journeyman is Alex Ybarra. ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate
Wall rough in ok cover storage room
ELE16-01838 Electrical Rough-In7/18/20167/18/20167/18/2016 2:27:17 PMPPART
level 6 stack 1 ceiling. Phone #: ###-#### Inspection requested via web by Brandon Robinson
Unable to inspect level 6 due to emergency and had to evacuate building.
Level 9 walls in rooms 939, 937, 936, 941, 913, 942, 911, 940, 938, 914, 945 coffee bar rough in ok cover.
ELE16-01984 Electrical Rough-In7/18/20167/18/20167/18/2016 12:59:04 PMPPASS
Would like call ahead; Frank Phone #: ###-#### Addition Rough in ok cover
ELE16-01082 Electrical Rough-In7/18/20167/18/20167/18/2016 12:37:38 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
Upstairs to remain unfinished with circuits for future. Basement not ready at this time. Main level rough in ok cover.
ELE16-00731 Final7/16/20167/18/20167/18/2016 11:35:13 AMAPASS
I will not be on site, please call with any questions. Phone #: ###-#### Inspection requested via web by Garrett Collins Final ok
ELE15-02279 Rough-In Permanent Service7/15/20167/18/20167/18/2016 10:03:36 AMAFAIL
The trailer is unoccupied. If you need to go in the key is in the A/C disconnect. The grounds and neutrals are separated in the trailer. Phone #: ###-#### Inspection requested via web by Craig Korell
110.26- Minimum work space shall be provided in front of service. 30" wide and 36" deep.
ELE16-02286 Rough-In Permanent Service7/17/20167/18/20167/18/2016 8:42:30 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Schroder
rough in ok cover p/s u/g n ok