ELE12-00404
| ELE-Aging Inspection | 7/18/2016 | 7/18/2016 | 7/19/2016 1:10:34 PM | | PASS |
|
|
Still under construction
|
ELE16-02289
| Final | 7/18/2016 | 7/18/2016 | 7/18/2016 3:57:55 PM | P | PASS |
|
|
Power for ADA doors. Contact Travis Hust Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
ELE16-02231
| Electrical Rough-In | 7/15/2016 | 7/18/2016 | 7/18/2016 3:56:52 PM | A | FAIL |
|
|
Jason Phone #: ###-#### 210.52- Receptacle outlets needed for wall spaces. Fixed panels of back slider are wall space and wall created by pocket door in office. 300.15- All NM cables shall terminate in a box. front patio light. 334.12- NM cable shall not be installed where subject to damage. Dining light switch leg stapled to wall surface. Contractor called end of day, stubs under house for floor receptacles, front lights to be mounted when beam layout is decided, and bed S/L fixed. Will recall.
|
ELE16-02289
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 3:36:18 PM | P | PASS |
|
|
Power for ADA doors. Contact Travis Hust Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek West entrance north set of doors only rough in ok.
|
ELE16-00151
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 3:34:10 PM | P | PASS |
|
|
Wall rough in inspection for cover. Contact is Eric Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Basement north of concrete dividing wall rough in ok cover
|
ELE15-00495
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 3:19:57 PM | P | PASS |
|
|
Can light ceiling inspection for cover high ceiling at column line A and B breeze way. Contact is Eric Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Breezeway lid complete rough in ok cover
|
ELE16-02290
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 2:46:59 PM | P | PASS |
|
|
Contact/Journeyman is Alex Ybarra. ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate Wall rough in ok cover storage room
|
ELE16-01838
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 2:27:17 PM | P | PART |
|
|
level 6 stack 1 ceiling. Phone #: ###-#### Inspection requested via web by Brandon Robinson Unable to inspect level 6 due to emergency and had to evacuate building. Level 9 walls in rooms 939, 937, 936, 941, 913, 942, 911, 940, 938, 914, 945 coffee bar rough in ok cover.
|
ELE16-01984
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 12:59:04 PM | P | PASS |
|
|
Would like call ahead; Frank Phone #: ###-#### Addition Rough in ok cover
|
ELE16-01082
| Electrical Rough-In | 7/18/2016 | 7/18/2016 | 7/18/2016 12:37:38 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard Upstairs to remain unfinished with circuits for future. Basement not ready at this time. Main level rough in ok cover.
|
ELE16-00731
| Final | 7/16/2016 | 7/18/2016 | 7/18/2016 11:35:13 AM | A | PASS |
|
|
I will not be on site, please call with any questions. Phone #: ###-#### Inspection requested via web by Garrett Collins Final ok
|
ELE15-02279
| Rough-In Permanent Service | 7/15/2016 | 7/18/2016 | 7/18/2016 10:03:36 AM | A | FAIL |
|
|
The trailer is unoccupied. If you need to go in the key is in the A/C disconnect. The grounds and neutrals are separated in the trailer. Phone #: ###-#### Inspection requested via web by Craig Korell 110.26- Minimum work space shall be provided in front of service. 30" wide and 36" deep.
|
ELE16-02286
| Rough-In Permanent Service | 7/17/2016 | 7/18/2016 | 7/18/2016 8:42:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder rough in ok cover p/s u/g n ok
|