Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00377 INSP-Final Inspection7/18/20177/18/20177/18/2017 2:25:55 PMPPASS
Final fire sprinkler inspection for area of work passed/complete.
FIR17-00377 INSP-Sprinkler Rough-in7/17/20177/18/20177/18/2017 2:25:21 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping/pendant heads complete, approved for cover.
FIR16-00519 INSP-Final Inspection7/17/20177/18/20177/18/2017 10:15:58 AMAPASS
Final fire alarm inspection for area of work passed/complete.
FIR17-00308 INSP-Sprinkler Rough-in7/17/20177/18/20177/18/2017 9:30:02 AMAFAIL
Multiple area's where piping is exposed to attic space, piping not covered with plastic sheeting, pocket will not be maintained between sheetrock and fire sprinkler piping, cover is not approved.
BLD17-00185 FIRE-Final Inspection7/18/20177/18/20177/18/2017 9:12:45 AMPPASS
No fire sprinklers, no fire alarms, fire extinguisher has current inspection tag and will be mounted in discussed location. Final life fire safety inspection passed/complete.
FIR16-00791 INSP-Sprinkler Rough-in/Hydro7/17/20177/18/20177/18/2017 8:30:58 AMAPASS
Rough to cover inspection for fire sprinkler piping/tenting complete, approved for cover.