MEC18-03407
| Final | 7/16/2018 | 7/18/2018 | 7/18/2018 4:21:45 PM | P | PASS |
|
|
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- furnace a/c coil co ok
|
MEC18-01782
| Final | 7/18/2018 | 7/18/2018 | 7/18/2018 3:54:54 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace final ok
|
MEC18-01799
| Final | 7/18/2018 | 7/18/2018 | 7/18/2018 3:22:24 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need duct blast test done- need to replace flex b vent on water heater remove screws that were installed at ceiling to hold into place(not locked into place)and install per manufactures installation manual
|
MEC18-03215
| Final | 7/18/2018 | 7/18/2018 | 7/18/2018 2:51:10 PM | P | PASS |
|
|
Please inspect before 3 PM Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co ok
|
MEC18-03471
| Final | 7/17/2018 | 7/18/2018 | 7/18/2018 2:32:08 PM | P | PASS |
|
|
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
|
MEC18-03488
| Final | 7/18/2018 | 7/18/2018 | 7/18/2018 1:59:28 PM | P | PASS |
|
|
Please call on way: Daniel ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- a/c coil co ok
|
MEC18-03362
| Final | 7/16/2018 | 7/18/2018 | 7/18/2018 1:52:50 PM | P | PASS |
|
|
PLEASE CALL HOMEOWNER SUSAN WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co ok
|
MEC18-03444
| Final | 7/18/2018 | 7/18/2018 | 7/18/2018 1:18:22 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC18-03460
| Rough-in | 7/18/2018 | 7/18/2018 | 7/18/2018 11:29:51 AM | P | CANC |
|
|
Light test on grease duct. Phone #: ###-#### >> Inspection requested via web by Drew Tverdy Inspection cancelled from web by: Drew Tverdy
|
MEC18-03385
| Rough-in | 7/17/2018 | 7/18/2018 | 7/18/2018 11:16:13 AM | A | PASS |
|
|
A.M.Mechanical Rough-in needed for Truck Stop you may contact Karl if you have any question ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin- R/I ok- seal on duct ok- ok for ceiling grid- will need R/A path to hallway by final
|
MEC18-01792
| Rough-in | 7/18/2018 | 7/18/2018 | 7/18/2018 11:00:05 AM | A | PART |
|
|
After 10 if possible. Ceiling grid cover inspection. Tha k You 2085730755 Inspection requested via web by william kerwin- need to add register to washer area by hood and omit 1 in that area- went over with installer- need access to duct detector above hard lid general contractor will take care of- need to finish sealing MAU duct - need time and a half tap on 16x14 supply duct in kitchen- recall in inspection when ready- no cover at this time
|
MEC18-01832
| Rough-in | 7/17/2018 | 7/18/2018 | 7/18/2018 10:54:14 AM | A | PASS |
|
|
Approve for cover Phone #: ###-#### Inspection requested via web by Dave DeChambeau- 2nd layer fire wrap ok- make up duct ok- ok for grid- will need fire gasket on all 3 curbs by final and plumbing vent 3 feet higher or 10 feet away from MAU
|
MEC18-03138
| Final | 7/16/2018 | 7/18/2018 | 7/18/2018 9:52:56 AM | P | PASS |
|
|
please call our install lead Owen when 30-45 mins in route so we can have flue pressured up in time. Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace(in crawl) a/c coil co ok
|
MEC18-03138
| Pressure Test | 7/18/2018 | 7/18/2018 | 7/18/2018 9:51:47 AM | A | PASS |
|
|
please call our install lead Owen when 30-45 mins in route so we can have flue pressured up in time. Phone #: ###-#### Inspection requested via web by Rick Montgomery- 5lb flue pass
|
MEC18-03056
| Final | 7/13/2018 | 7/18/2018 | 7/18/2018 9:17:45 AM | A | PASS |
|
|
Please call on way: Sean ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- a/c coil co ok
|
MEC18-01955
| Final | 7/17/2018 | 7/18/2018 | 7/18/2018 8:40:57 AM | A | PASS |
|
|
MEC AND FIREPL GARAGE CODE 7373 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
|
MEC17-02368
| Mec-Aging Inspection | 7/18/2018 | 7/18/2018 | 7/18/2018 8:18:45 AM | | FAIL |
|
|
contractor needs to schedule inspection with homeowner
|
MEC17-02360
| Mec-Aging Inspection | 7/18/2018 | 7/18/2018 | 7/18/2018 8:17:57 AM | | FAIL |
|
|
needs final called in
|
MEC17-01076
| Mec-Aging Inspection | 7/18/2018 | 7/18/2018 | 7/18/2018 8:17:21 AM | | DONE |
|
|
|
MEC17-01076
| DOC - Permit Expired | 7/18/2018 | 7/18/2018 | 7/18/2018 8:17:11 AM | A | PASS |
|
|
no calls-
|