Inspections for the day of: Wednesday, July 18, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00209 INSP-Sprinkler Rough-in7/18/20187/18/20187/18/2018 1:41:54 PMPPART
Rough to cover inspection for overehad fire sprinkler piping complete. Overhead fire sprinkler located between conditioned spaces approved for cover. Overhead fire sprinkler piping located in attic spaces or below unconditioned spaces cannot be covered until a tenting inspection is complete. Any cover that is installed before tenting inspection will be removed to verify tenting is in place.

Need a rough to cover on the 1st and second floors so they can insulate. We will have you back out for a second rough in inspection for the attic piping tenting prior to sheet rock Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-00778 FIRE-Final Inspection7/18/20187/18/20187/18/2018 1:37:26 PMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.

Ken Phone #: ###-####
BLD18-00777 FIRE-Final Inspection7/18/20187/18/20187/18/2018 1:36:56 PMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection complete.

Ken Phone #: ###-####
FIR18-00290 INSP-Final Inspection7/17/20187/18/20187/18/2018 9:21:40 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD18-00805 FIRE-Final Inspection7/17/20187/18/20187/18/2018 9:00:54 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is located by the fire pump/riser room. Final life fire safety inspection complete.

Tim Phone #: ###-####
BLD17-02817 FIRE-Final Inspection7/17/20187/18/20187/18/2018 9:00:34 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is located by the fire pump/riser room. Final life fire safety inspection complete.

Tim Phone #: ###-####
FIR18-00297 INSP-Final Inspection7/18/20187/18/20187/18/2018 8:58:33 AMAPASS
Final fire sprinkler inspection for area of work complete.
FIR18-00363 INSP-Final Inspection7/18/20187/18/20187/18/2018 8:58:05 AMAPASS
Final fire alarm inspection for area of work complete.