BLD06-00960
| FIRE-Final Inspection | 7/18/2006 | 7/19/2006 | 7/20/2006 8:13:46 AM | A | PASS |
|
|
Life safety passed field inspection.
|
FIR06-00335
| INSP-Final Inspection | 7/19/2006 | 7/19/2006 | 7/20/2006 8:12:05 AM | P | PASS |
|
|
Fire sprinkler passed final inspection.
|
MIS06-00179
| FIR-Final | 7/18/2006 | 7/19/2006 | 7/19/2006 1:45:35 PM | P | PASS |
|
|
Items on previous c/n have been completed.
|
FIR05-00854
| INSP-Final Inspection | 7/18/2006 | 7/19/2006 | 7/19/2006 1:16:33 PM | A | PART |
|
|
Need to provide test certification for the backflow preventer prior to final, need to secure main control valves as required. Also NOTE: The overhead system piping was connected and filled using the UG supply prior to field inspection of the UG line flush as required, sprinkler contractor is aware of code violation. Line flush performed post OH system fill. Remaining final inspection items are satisfactory.
|
FIR06-00163
| INSP-Final Inspection | 7/18/2006 | 7/19/2006 | 7/19/2006 11:57:29 AM | A | PASS |
|
|
Fire alarm work is satisfactory, inspection passed.
|