ELE07-02451
| Temporary Service | 7/19/2007 | 7/19/2007 | 7/20/2007 7:59:27 AM | P | CANC |
|
|
Temp Service inspect. Please Call Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson met contr, see conf
|
ELE07-02546
| Temporary Service | 7/19/2007 | 7/19/2007 | 7/20/2007 7:38:28 AM | P | NH |
|
|
for a t/p corey- ###-#### called contr, no tools to access gate
|
ELE07-01624
| Temporary Service | 7/19/2007 | 7/19/2007 | 7/19/2007 4:05:07 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 7/19/2007 at 8:50:55 AM. Contact: ###-####. wrong type request, see ri
|
ELE07-01624
| Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 3:33:54 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/19/2007 at 8:50:55 AM. Contact: ###-####. u/g ok to cover for services to temp power spots
|
ELE07-02554
| Rough-In Permanent Service | 7/19/2007 | 7/19/2007 | 7/19/2007 3:28:00 PM | P | PASS |
|
|
rick - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok , p/s u/g n ok
|
ELE07-02241
| Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 2:55:38 PM | P | FAIL |
|
|
dan - ok to cover on the walls only Phone #: ###-#### called left corr notice, nec 330.30 (B) mc cable shall be strapped within 12" of box, 110.12(A) unused openings shall be closed, 100.3(B) shall use approved equipment and per mfgr's instructions, BCC all make-up shall be done, no wiring in valley of framing members shall be done, address shall be posted
|
ELE07-01321
| Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 2:31:35 PM | P | PASS |
|
|
x-ray room ok to cover ceiling
|
ELE07-01321
| Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 2:30:12 PM | P | CANC |
|
|
matt Note: grid Phone #: ###-####
|
ELE06-03701
| Final | 7/19/2007 | 7/19/2007 | 7/19/2007 1:42:50 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/19/2007 at 9:16:16 AM. Contact: ###-####. ok to final
|
ELE07-02550
| Final | 7/19/2007 | 7/19/2007 | 7/19/2007 12:59:57 PM | P | PASS |
|
|
###-#### Pat ok to final
|
ELE07-02550
| Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 12:59:07 PM | P | PASS |
|
|
###-#### Pat ric ok
|
ELE07-01551
| Electrical Rough-In | 7/19/2007 | 7/19/2007 | 7/19/2007 12:26:48 PM | P | PASS |
|
|
joe Note: ufer ground Phone #: ###-#### ok to pour concrete encased electrode
|
ELE07-02471
| Rough-In Permanent Service | 7/18/2007 | 7/19/2007 | 7/19/2007 11:46:18 AM | A | FAIL |
|
|
Approval for cover & sub-panel inspection. Upstairs & downstairs. Please use front door. Phone #: ###-#### Internet Inspection Request from: Kathy Briggs called,left essage, left corr notice, nec 300.4(A) edge of bored holes and raceways shall be 1 1/4" from edge of framing members( includes lv), 250.148(B) grounding in box shall be such that device removal does not interfere with continuity of grounding, 362.26 there shall not be over 360 degrees bend in ent, BCC all u/g shall be seen before cover
|
ELE07-02537
| Electrical Rough-In | 7/18/2007 | 7/19/2007 | 7/19/2007 10:28:13 AM | A | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok, met elect
|
ELE07-01626
| Final | 7/18/2007 | 7/19/2007 | 7/19/2007 9:43:12 AM | A | PASS |
|
|
door code is 8834 Phone #: ###-#### Internet Inspection Request from: Paul Schepper ok to final
|
ELE07-00889
| Permanent Service | 7/19/2007 | 7/19/2007 | 7/19/2007 8:35:21 AM | P | PASS |
|
|
randy Phone #: ###-#### Internet Inspection Request from: Loren Ramsey p/s u/g n ok
|
ELE07-00940
| Electrical Rough-In | 7/18/2007 | 7/19/2007 | 7/19/2007 8:32:32 AM | A | PASS |
|
|
michael - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok, owner provided 2" concrete encasement around riser
|
ELE07-02451
| Electrical Rough-In | 7/18/2007 | 7/19/2007 | 7/19/2007 7:56:21 AM | A | PASS |
|
|
Light Pole Bases inspection. Please call James K. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson looked at u/g raceways, ok to backfill
|