Inspections for the day of: Thursday, July 19, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02451 Temporary Service7/19/20077/19/20077/20/2007 7:59:27 AMPCANC
Temp Service inspect. Please Call Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson met contr, see conf
ELE07-02546 Temporary Service7/19/20077/19/20077/20/2007 7:38:28 AMPNH
for a t/p corey- ###-#### called contr, no tools to access gate
ELE07-01624 Temporary Service7/19/20077/19/20077/19/2007 4:05:07 PMPCANC
Scheduled by a contractor via Hello! on 7/19/2007 at 8:50:55 AM. Contact: ###-####. wrong type request, see ri
ELE07-01624 Electrical Rough-In7/19/20077/19/20077/19/2007 3:33:54 PMPPASS
Scheduled by a contractor via Hello! on 7/19/2007 at 8:50:55 AM. Contact: ###-####. u/g ok to cover for services to temp power spots
ELE07-02554 Rough-In Permanent Service7/19/20077/19/20077/19/2007 3:28:00 PMPPASS
rick - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok , p/s u/g n ok
ELE07-02241 Electrical Rough-In7/19/20077/19/20077/19/2007 2:55:38 PMPFAIL
dan - ok to cover on the walls only Phone #: ###-#### called left corr notice, nec 330.30 (B) mc cable shall be strapped within 12" of box, 110.12(A) unused openings shall be closed, 100.3(B) shall use approved equipment and per mfgr's instructions, BCC all make-up shall be done, no wiring in valley of framing members shall be done, address shall be posted
ELE07-01321 Electrical Rough-In7/19/20077/19/20077/19/2007 2:31:35 PMPPASS
x-ray room ok to cover ceiling
ELE07-01321 Electrical Rough-In7/19/20077/19/20077/19/2007 2:30:12 PMPCANC
matt Note: grid Phone #: ###-####
ELE06-03701 Final7/19/20077/19/20077/19/2007 1:42:50 PMPPASS
Scheduled by a contractor via Hello! on 7/19/2007 at 9:16:16 AM. Contact: ###-####. ok to final
ELE07-02550 Final7/19/20077/19/20077/19/2007 12:59:57 PMPPASS
###-#### Pat ok to final
ELE07-02550 Electrical Rough-In7/19/20077/19/20077/19/2007 12:59:07 PMPPASS
###-#### Pat ric ok
ELE07-01551 Electrical Rough-In7/19/20077/19/20077/19/2007 12:26:48 PMPPASS
joe Note: ufer ground Phone #: ###-#### ok to pour concrete encased electrode
ELE07-02471 Rough-In Permanent Service7/18/20077/19/20077/19/2007 11:46:18 AMAFAIL
Approval for cover & sub-panel inspection. Upstairs & downstairs. Please use front door. Phone #: ###-#### Internet Inspection Request from: Kathy Briggs called,left essage, left corr notice, nec 300.4(A) edge of bored holes and raceways shall be 1 1/4" from edge of framing members( includes lv), 250.148(B) grounding in box shall be such that device removal does not interfere with continuity of grounding, 362.26 there shall not be over 360 degrees bend in ent, BCC all u/g shall be seen before cover
ELE07-02537 Electrical Rough-In7/18/20077/19/20077/19/2007 10:28:13 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok, met elect
ELE07-01626 Final7/18/20077/19/20077/19/2007 9:43:12 AMAPASS
door code is 8834 Phone #: ###-#### Internet Inspection Request from: Paul Schepper ok to final
ELE07-00889 Permanent Service7/19/20077/19/20077/19/2007 8:35:21 AMPPASS
randy Phone #: ###-#### Internet Inspection Request from: Loren Ramsey p/s u/g n ok
ELE07-00940 Electrical Rough-In7/18/20077/19/20077/19/2007 8:32:32 AMAPASS
michael - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ric ok, owner provided 2" concrete encasement around riser
ELE07-02451 Electrical Rough-In7/18/20077/19/20077/19/2007 7:56:21 AMAPASS
Light Pole Bases inspection. Please call James K. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson looked at u/g raceways, ok to backfill