FIR06-00011
| INSP-Alarm Testing | 7/19/2007 | 7/19/2007 | 7/19/2007 6:24:34 PM | P | DONE |
|
|
See Mike Timmermans notes and the city approved plans for devices tested.
|
FIR07-00103
| INSP-Final Inspection | 7/18/2007 | 7/19/2007 | 7/19/2007 6:23:19 PM | P | CANC |
|
|
Was to be called in when the fire alarm was ready. It wasn't
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 7/18/2007 | 7/19/2007 | 7/19/2007 3:43:31 PM | A | PART |
|
|
The hydro test for the first floor southwest quadrant passed. The rough-in failed since the floor plan does not match the plans. I told both the fire sprinkler contractor and the general contractor I would not give permission to cover. The general contractor stated he was going to cover the piping no matter what and would deal with the reperconssions later.
|
BLD07-01476
| FIRE-Final Inspection | 7/18/2007 | 7/19/2007 | 7/19/2007 3:32:29 PM | A | PASS |
|
|
Life safety passed
|
FIR07-00448
| INSP-Sprinkler Rough-in/Hydro | 7/18/2007 | 7/19/2007 | 7/19/2007 3:16:30 PM | P | PART |
|
|
Underground hydro test passed but the overhead would not hold pressure.
|
BLD06-00205
| FIRE-Final Inspection | 7/18/2007 | 7/19/2007 | 7/19/2007 12:21:26 PM | A | FAIL |
|
|
No inspection performed. Needs fire sprinkler final first.
|
FIR05-00536
| INSP-Sprinkler Rough-in/Hydro | 7/18/2007 | 7/19/2007 | 7/19/2007 11:43:31 AM | A | PASS |
|
|
The remaining areas of the central tower 2nd floor are ok to cover.
|
FIR07-00513
| INSP-Final Inspection | 7/18/2007 | 7/19/2007 | 7/19/2007 10:54:06 AM | A | FAIL |
|
|
The two burner stove needs to be placed under the hood per IMC and I need verification that a type one hood with suppresion is not required for the pizza oven. The trip test of the hoods passed.
|
BLD07-01663
| FIRE-Final Inspection | 7/17/2007 | 7/19/2007 | 7/19/2007 9:54:27 AM | A | PASS |
|
|
Life safety passed. The scope of work referenced sprinklers but there are none in the building. Owner to get the occupant load sign posted prior to the structural inspection.
|