Inspections for the day of: Friday, July 19, 2013.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01431 FIRE-Final Inspection7/16/20137/19/20137/19/2013 4:24:20 PMPFAIL
Need annual inspection for the fire extinguisher and door hardware corrected for exiting/access to the island restrooms that were not shown on the plans. Per email from tim woodard "Talking with Carl Westfall I learned one of the ways we deal with that scenario on existing cases like this would be to only have a key locking dead bolt (Both sides). They would need to sign each side “THIS DOOR TO REMAIN UNLOCKED WHEN RESTROOM CORE IS OCCUPIED”. This eliminates the idea of someone besides staff being able to lock people inside that core area. Furthermore by the wording of “RESTROOM CORE” the associate who would be locking the door would hopefully have enough of a trigger to check the restrooms prior to locking them down.
BLD13-01394 FIRE-Final Inspection7/18/20137/19/20137/19/2013 4:07:26 PMPFAIL
Per scott arellano a temporary occupancy is ok if the sprinkler system in the paint booth is functional. When I arrived at the job site I found the new system still in the process of being installed. I spoke to Loyd about what was needed and we agreed to call the inspection back in for monday morning at which time the sprinkler work should be completed.
FIR13-00270 INSP-Sprinkler Rough-in7/19/20137/19/20137/19/2013 4:04:36 PMPPASS
OK to coversoffit at fish counter
FIR13-00269 INSP-Sprinkler Rough-in7/19/20137/19/20137/19/2013 4:02:32 PMPPASS
OK to cover bakery freezer. The two dry pendants have been added behind the condensors.
BLD13-00985 FIRE-Final Inspection7/19/20137/19/20137/19/2013 4:01:10 PMPCANC
To be canceled per brian and will be rescheduled for monday.
FIR13-00248 INSP-Sprinkler Rough-in7/18/20137/19/20137/19/2013 3:58:56 PMPCANC
Wrong permit number number called in. The two correct permit numbers are called in for mandya to make the entries. They are FIR13-00249 and 250. Each of these underground supply lines is ok for cover as marked on the city approved plans.
FIR13-00163 INSP-Sprinkler Rough-in7/18/20137/19/20137/19/2013 11:48:19 AMAPASS
See areas marked "ok" where piping is ok to cover.
FIR13-00095 INSP-Sprinkler Rough-in7/18/20137/19/20137/19/2013 10:39:33 AMAPASS
Rough-in now matches the plan modification.
BLD13-00849 FIRE-Final Inspection7/17/20137/19/20137/19/2013 10:38:41 AMAPASS
Life safety passed
FIR13-00227 INSP-Final Inspection7/18/20137/19/20137/19/2013 9:46:37 AMAPASS
Permit finaled
FIR13-00182 INSP-Alarm Testing7/17/20137/19/20137/19/2013 9:11:28 AMADONE
Completed the Gym Area which included corridors and dressing rooms. Corrections have been made as noted on the previous correction notice. However it appears notification is missing from a small restroom as noted on the plans.
FIR13-00274 INSP-Final Inspection7/18/20137/19/20137/19/2013 9:06:31 AMAPART
The two smoke detectors in the Dry Storage tested ok. The city approved plans only show one smoke detector. As-builts will need to be provided.