BLD13-01431
| FIRE-Final Inspection | 7/16/2013 | 7/19/2013 | 7/19/2013 4:24:20 PM | P | FAIL |
|
|
Need annual inspection for the fire extinguisher and door hardware corrected for exiting/access to the island restrooms that were not shown on the plans. Per email from tim woodard "Talking with Carl Westfall I learned one of the ways we deal with that scenario on existing cases like this would be to only have a key locking dead bolt (Both sides). They would need to sign each side “THIS DOOR TO REMAIN UNLOCKED WHEN RESTROOM CORE IS OCCUPIED”. This eliminates the idea of someone besides staff being able to lock people inside that core area. Furthermore by the wording of “RESTROOM CORE” the associate who would be locking the door would hopefully have enough of a trigger to check the restrooms prior to locking them down.
|
BLD13-01394
| FIRE-Final Inspection | 7/18/2013 | 7/19/2013 | 7/19/2013 4:07:26 PM | P | FAIL |
|
|
Per scott arellano a temporary occupancy is ok if the sprinkler system in the paint booth is functional. When I arrived at the job site I found the new system still in the process of being installed. I spoke to Loyd about what was needed and we agreed to call the inspection back in for monday morning at which time the sprinkler work should be completed.
|
FIR13-00270
| INSP-Sprinkler Rough-in | 7/19/2013 | 7/19/2013 | 7/19/2013 4:04:36 PM | P | PASS |
|
|
OK to coversoffit at fish counter
|
FIR13-00269
| INSP-Sprinkler Rough-in | 7/19/2013 | 7/19/2013 | 7/19/2013 4:02:32 PM | P | PASS |
|
|
OK to cover bakery freezer. The two dry pendants have been added behind the condensors.
|
BLD13-00985
| FIRE-Final Inspection | 7/19/2013 | 7/19/2013 | 7/19/2013 4:01:10 PM | P | CANC |
|
|
To be canceled per brian and will be rescheduled for monday.
|
FIR13-00248
| INSP-Sprinkler Rough-in | 7/18/2013 | 7/19/2013 | 7/19/2013 3:58:56 PM | P | CANC |
|
|
Wrong permit number number called in. The two correct permit numbers are called in for mandya to make the entries. They are FIR13-00249 and 250. Each of these underground supply lines is ok for cover as marked on the city approved plans.
|
FIR13-00163
| INSP-Sprinkler Rough-in | 7/18/2013 | 7/19/2013 | 7/19/2013 11:48:19 AM | A | PASS |
|
|
See areas marked "ok" where piping is ok to cover.
|
FIR13-00095
| INSP-Sprinkler Rough-in | 7/18/2013 | 7/19/2013 | 7/19/2013 10:39:33 AM | A | PASS |
|
|
Rough-in now matches the plan modification.
|
BLD13-00849
| FIRE-Final Inspection | 7/17/2013 | 7/19/2013 | 7/19/2013 10:38:41 AM | A | PASS |
|
|
Life safety passed
|
FIR13-00227
| INSP-Final Inspection | 7/18/2013 | 7/19/2013 | 7/19/2013 9:46:37 AM | A | PASS |
|
|
Permit finaled
|
FIR13-00182
| INSP-Alarm Testing | 7/17/2013 | 7/19/2013 | 7/19/2013 9:11:28 AM | A | DONE |
|
|
Completed the Gym Area which included corridors and dressing rooms. Corrections have been made as noted on the previous correction notice. However it appears notification is missing from a small restroom as noted on the plans.
|
FIR13-00274
| INSP-Final Inspection | 7/18/2013 | 7/19/2013 | 7/19/2013 9:06:31 AM | A | PART |
|
|
The two smoke detectors in the Dry Storage tested ok. The city approved plans only show one smoke detector. As-builts will need to be provided.
|