ELE13-00835
| ELE-Aging Inspection | 7/19/2016 | 7/19/2016 | 7/25/2016 7:57:45 AM | | CANC |
|
|
too busy
|
ELE13-00542
| ELE-Aging Inspection | 7/19/2016 | 7/19/2016 | 7/25/2016 7:56:07 AM | | CANC |
|
|
too busy
|
ELE16-01165
| Permanent Service | 7/19/2016 | 7/19/2016 | 7/19/2016 2:04:55 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Buster Bowen p/s u/g n ok 3 phase meter
|
ELE16-01873
| Final | 7/18/2016 | 7/19/2016 | 7/19/2016 1:18:03 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Shane Dale 406.6 faceplates required(in cabinet) 314.20 receptacles behind combustile material shall have a listed extender(in cabinet) 110.12(a) unused openings shall be closed(cieling)
|
ELE16-02141
| Rough-In Permanent Service | 7/19/2016 | 7/19/2016 | 7/19/2016 12:49:58 PM | P | PASS |
|
|
This is the inspection for the Shop. Phone #: ###-#### Inspection requested via web by Darryn Coburn detached garage ok cover
|
ELE16-02130
| Electrical Rough-In | 7/18/2016 | 7/19/2016 | 7/19/2016 11:30:56 AM | A | FAIL |
|
|
Nail plates installed and grounding conductor run from outside to inside. Phone #: ###-#### Inspection requested via web by Zac Bentz too many violations to list. need kitchen layout or hire a contractor to finish project
|
ELE16-02295
| Final | 7/18/2016 | 7/19/2016 | 7/19/2016 10:30:11 AM | A | CANC |
|
|
Inspection requested via web by CHRIS CARMINE needed p/s
|
ELE16-02295
| Permanent Service | 7/19/2016 | 7/19/2016 | 7/19/2016 9:54:19 AM | P | PART |
|
|
Inspection requested via web by CHRIS CARMINE p/s u/g rec ok 1 three phase meter needed
|
ELE16-02302
| Permanent Service | 7/19/2016 | 7/19/2016 | 7/19/2016 9:35:32 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jerry Moore p/s u/g rec ok
|
ELE16-02267
| Rough-In Permanent Service | 7/18/2016 | 7/19/2016 | 7/19/2016 8:37:43 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn rough-in ok cover p/s u/g n ok
|