BLD16-01280
| FIRE-Final Inspection | 7/18/2016 | 7/19/2016 | 7/19/2016 12:04:18 PM | A | FAIL |
|
|
Still need the project related fire alarm permit addressed.
|
BLD16-01400
| FIRE-Final Inspection | 7/18/2016 | 7/19/2016 | 7/19/2016 11:16:07 AM | A | FAIL |
|
|
Need the exit discharge lighting installed/tested.
|
FIR16-00436
| INSP-Final Inspection | 7/18/2016 | 7/19/2016 | 7/19/2016 10:12:29 AM | A | FAIL |
|
|
Relocate or add strobe as discussed in the bedroom, revise plans to show a horn being installed in the corridor as shown on the approved plans. See note on monitoring in electronic permit activities.
|
FIR16-00451
| INSP-Final Inspection | 7/18/2016 | 7/19/2016 | 7/19/2016 9:45:54 AM | A | FAIL |
|
|
The east hvac unit tested ok. The west hvac unit would not go into heat mode for testing.
|
NAF16-00049
| INSP-Conference | 7/19/2016 | 7/19/2016 | 7/19/2016 9:39:36 AM | P | CANC |
|
|
Call prior to going Phone #: 8615838 >> Inspection requested via mobile web by Denton Inspection cancelled via mobile web on Tuesday, July 19, 2016.
|
FIR16-00369
| INSP-Final Inspection | 7/18/2016 | 7/19/2016 | 7/19/2016 9:10:39 AM | A | PASS |
|
|
Permit finaled
|
BLD16-02557
| FIRE-Final Inspection | 7/19/2016 | 7/19/2016 | 7/19/2016 12:00:00 AM | P | DONE |
|
|
|
FIR16-00425
| INSP-Final Inspection | 7/18/2016 | 7/19/2016 | 7/18/2016 12:00:00 AM | A | DONE |
|
|
Ok to sign off by Troy Cobbley.
|