Inspections for the day of: Tuesday, July 19, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00040 INSP-Sprinkler Rough-in/Hydro7/19/20167/19/20167/19/2016 2:30:48 PMPCANC
Inspection request rescheduled for 20JULY16.
FIR15-00808 INSP-Sprinkler Rough-in7/18/20167/19/20167/19/2016 10:39:49 AMAPART
Rough to cover/tenting inspection for overhead fire sprinkler piping complete for northeast section of level 3, overhead fire sprinkler piping in the northeast section of level 3 approved for cover.
FIR16-00314 INSP-Sprinkler Rough-in7/18/20167/19/20167/19/2016 10:06:11 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, level 2 overhead fire sprinkler piping approved for cover.
BLD15-01107 FIRE-Final Inspection7/18/20167/19/20167/19/2016 9:10:44 AMACANC
Final life fire safety inspection could not be completed, this BLD permit has an FIR permit that is not attched under project related cases, FIR16-00380, permit is still under review. FIR permit needs to be in issued status for final life fire safety inspection can be performed, inspection request cancelled.