Inspections for the day of: Wednesday, July 19, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01776 Electrical Rough-In7/19/20177/19/20177/19/2017 2:13:10 PMPPASS
Ceiling Phone #: ###-#### Inspection requested via web by Jim Williams
Corridor not ready. TI grid rough in ok cover
MIS17-00225 ELE-Conference7/18/20177/19/20177/19/2017 12:53:37 PMAFAIL
as per Eric Strole work w/o permits
Unable to gain access to interior. Observed building materials through door window. BCC 4-05-18. Electrical permit required prior to start of work. Posted notice
ELE17-01574 Final7/18/20177/19/20177/19/2017 10:59:20 AMAPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE17-01776 Electrical Rough-In7/19/20177/19/20177/19/2017 10:16:05 AMANR
Ceiling Phone #: ###-#### Inspection requested via web by Jim Williams
300.11- All luminaires shall be supported independant of grid. Grid wires installed but not installed on luminaires yet. Will recall
ELE17-02174 Final7/18/20177/19/20177/19/2017 10:14:47 AMANR
garage code 0324 Phone #: ###-#### Inspection requested via web by Darryn Coburn
rough in done on 7-17-17. requested wrong job.
ELE17-01282 Final7/18/20177/19/20177/19/2017 10:11:09 AMAFAIL
garage code 1524 Phone #: ###-#### Inspection requested via web by Darryn Coburn
422.11(A)- Branch circuit and overcurrent device shall be sized as per manufacturers instructions. 15 amp installed, 20 amp and 12ga. min.noted.