Inspections for the day of: Thursday, July 19, 2018.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02600 Electrical Rough-In7/18/20187/19/20187/19/2018 2:13:09 PMPNR
Brian Prussia, crew lead.
Install is taking place on 7/19 at 1 pm. Phone #: ###-#### Inspection requested via web by BRS Permitting
No one on site. Called contact which stated job has been rescheduled to next week but forgot to call and cancel inspection. Will recall when ready.
ELE18-02711 Final7/18/20187/19/20187/19/2018 10:19:23 AMAPASS
Final Phone #: ###-#### Inspection requested via web by JENNY EMEL Final ok
ELE18-02711 Electrical Rough-In7/18/20187/19/20187/19/2018 10:18:54 AMAPASS
Ceiling for cover Phone #: ###-#### Inspection requested via web by JENNY EMEL
Grid rough in ok cover
ELE18-02231 Conference7/18/20187/19/20187/19/2018 9:41:54 AMADONE
Please call Brandon Sailors a call 30 minutes prior to anticipated arrival time. THANKS Phone #: ###-#### Inspection requested via web by Kelly Tarter Discussed requirements for changing or refeeding services all changing from overhead to underground.
Each service shall have a permit.
Grounding electrode system shall be installed on each service.
Available fault current shall posted prior to inspections, at least provide AFC value to ensure main breakers cover value. Not needed on services with no changes.
All bonding shall be complete if needed. Some have IMC service risers and metallic nipples being installed.
Inspections will not need after hours inspections. Contractor to have all grounding electrodes in place, and will confirm bonding if needed on final.
Some services to be reconnected with no changes needed.