MEC18-03518
| Rough-in | 7/19/2018 | 7/19/2018 | 7/20/2018 2:01:45 PM | P | DONE |
|
|
Please meet plumbing inspector at residence at 1:30PM on 07/19/2018. Thank you! Phone #: ###-#### Inspection requested via web by Nicole Yogerst- went over furnace a/c install- will need a flue test 5 psi on 15 psi gauge max
|
MEC18-03243
| Rough-in | 7/19/2018 | 7/19/2018 | 7/19/2018 4:10:48 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- seal on all duct ok- missing 1 heat pump unit - will inspect when installed- ok for floating grid
|
MEC18-03514
| Final | 7/18/2018 | 7/19/2018 | 7/19/2018 3:47:28 PM | P | PASS |
|
|
please call our lead installer Jonah when 30 mins in route. afternoon would be preferred please, 3-5p Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co ok
|
MEC18-03494
| Final | 7/19/2018 | 7/19/2018 | 7/19/2018 3:24:13 PM | P | PASS |
|
|
If you could please Call Skip when you head his way that would be great. He is installing it today so later this afternoon would super. thank you so much! Phone #: ###-#### Inspection requested via web by Devony Bullard- electric furnace heat pump ok
|
MEC18-02215
| Conference | 7/19/2018 | 7/19/2018 | 7/19/2018 3:07:34 PM | P | CANC |
|
|
at 200pm meet with Troy- Discussed issues forgrease duct serving 2 tables- Karl will make mock up and meet again-
|
MEC18-01792
| Rough-in | 7/19/2018 | 7/19/2018 | 7/19/2018 12:21:13 PM | P | PASS |
|
|
Ceiling grid cover. Bj 2085730755 Inspection requested via web by william kerwin- R/I ok- ok for ceiling tiles
|
MEC18-03357
| Final | 7/18/2018 | 7/19/2018 | 7/19/2018 11:39:05 AM | A | NH |
|
|
In the AM, but not first thing. Please call on way: Joseph Phone #: ###-#### Inspection requested via web by Krista Boss- no one home
|
MEC17-05748
| Final | 7/19/2018 | 7/19/2018 | 7/19/2018 11:18:45 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Devony Bullard- final ok
|
MEC18-02797
| Final | 7/16/2018 | 7/19/2018 | 7/19/2018 11:07:18 AM | P | PASS |
|
|
Ashley will meet you there--call her at ###-#### about 15 mins before, no need to call management. I will get a key from property management and meet you there. Phone #: ###-#### Inspection requested via web by Michael Stimpson- a/c coil co ok
|
MEC18-03409
| Pressure Test | 7/18/2018 | 7/19/2018 | 7/19/2018 10:27:55 AM | A | FAIL |
|
|
Pressure Test and rough in Phone #: ###-#### Inspection requested via web by Randy Hart- gauge wont zero out
|
MEC18-03409
| Rough-in | 7/19/2018 | 7/19/2018 | 7/19/2018 10:27:37 AM | A | FAIL |
|
|
Pressure Test and rough in Phone #: ###-#### Inspection requested via web by Randy Hart- need approved Manual J onsite couldnt find one- need to seal exhaust fan pentrations at fan- need to secure gas piping to trusses in garage-
|
MEC18-03410
| Rough-in | 7/18/2018 | 7/19/2018 | 7/19/2018 10:26:07 AM | A | PASS |
|
|
Gas Fireplace rough in Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace R/I ok
|
MEC18-02914
| Rough-in | 7/18/2018 | 7/19/2018 | 7/19/2018 9:54:48 AM | A | FAIL |
|
|
Alex Phone #: ###-####- insulation shield on b vent in garage needs 1" clearance- need to seal all boots to floor- need to insulate supply duct in crawl between joists- need framing complete around supply and return air in stairwell- need flue test gauge at zero
|
MEC18-03501
| Final | 7/18/2018 | 7/19/2018 | 7/19/2018 9:22:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Teresa Costello- furnace a/c coil co ok
|
MEC18-03339
| Final | 7/17/2018 | 7/19/2018 | 7/19/2018 9:05:49 AM | A | PASS |
|
|
Please call the Owner, Kelli at ###-#### with a 30 minute heads up arrival time. Thank you! Phone #: ###-#### Inspection requested via web by David or K Cole- furnace coil co ok
|
MEC18-02125
| Final | 7/18/2018 | 7/19/2018 | 7/19/2018 8:34:13 AM | A | PASS |
|
|
Final Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
MEC16-02807
| Mec-Aging Inspection | 7/19/2018 | 7/19/2018 | 7/19/2018 8:04:18 AM | | DONE |
|
|
|
MEC16-02807
| DOC - Permit Expired | 7/19/2018 | 7/19/2018 | 7/19/2018 8:04:08 AM | A | PASS |
|
|
bldg permit expired
|
MEC17-03433
| Mec-Aging Inspection | 7/19/2018 | 7/19/2018 | 7/19/2018 8:03:28 AM | | FAIL |
|
|
still waiting on final inspection to be scheduled by contractor
|