Inspections for the day of: Thursday, July 19, 2018.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03518 Rough-in7/19/20187/19/20187/20/2018 2:01:45 PMPDONE
Please meet plumbing inspector at residence at 1:30PM on 07/19/2018. Thank you! Phone #: ###-#### Inspection requested via web by Nicole Yogerst- went over furnace a/c install- will need a flue test 5 psi on 15 psi gauge max
MEC18-03243 Rough-in7/19/20187/19/20187/19/2018 4:10:48 PMPPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige- seal on all duct ok- missing 1 heat pump unit - will inspect when installed- ok for floating grid
MEC18-03514 Final7/18/20187/19/20187/19/2018 3:47:28 PMPPASS
please call our lead installer Jonah when 30 mins in route. afternoon would be preferred please, 3-5p Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co ok
MEC18-03494 Final7/19/20187/19/20187/19/2018 3:24:13 PMPPASS
If you could please Call Skip when you head his way that would be great. He is installing it today so later this afternoon would super. thank you so much! Phone #: ###-#### Inspection requested via web by Devony Bullard- electric furnace heat pump ok
MEC18-02215 Conference7/19/20187/19/20187/19/2018 3:07:34 PMPCANC
at 200pm meet with Troy- Discussed issues forgrease duct serving 2 tables- Karl will make mock up and meet again-
MEC18-01792 Rough-in7/19/20187/19/20187/19/2018 12:21:13 PMPPASS
Ceiling grid cover. Bj 2085730755 Inspection requested via web by william kerwin- R/I ok- ok for ceiling tiles
MEC18-03357 Final7/18/20187/19/20187/19/2018 11:39:05 AMANH
In the AM, but not first thing. Please call on way: Joseph Phone #: ###-#### Inspection requested via web by Krista Boss- no one home
MEC17-05748 Final7/19/20187/19/20187/19/2018 11:18:45 AMPPASS
Phone #: ###-#### Inspection requested via web by Devony Bullard- final ok
MEC18-02797 Final7/16/20187/19/20187/19/2018 11:07:18 AMPPASS
Ashley will meet you there--call her at ###-#### about 15 mins before, no need to call management.
I will get a key from property management and meet you there. Phone #: ###-#### Inspection requested via web by Michael Stimpson- a/c coil co ok
MEC18-03409 Pressure Test7/18/20187/19/20187/19/2018 10:27:55 AMAFAIL
Pressure Test and rough in Phone #: ###-#### Inspection requested via web by Randy Hart- gauge wont zero out
MEC18-03409 Rough-in7/19/20187/19/20187/19/2018 10:27:37 AMAFAIL
Pressure Test and rough in Phone #: ###-#### Inspection requested via web by Randy Hart- need approved Manual J onsite couldnt find one- need to seal exhaust fan pentrations at fan- need to secure gas piping to trusses in garage-
MEC18-03410 Rough-in7/18/20187/19/20187/19/2018 10:26:07 AMAPASS
Gas Fireplace rough in Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace R/I ok
MEC18-02914 Rough-in7/18/20187/19/20187/19/2018 9:54:48 AMAFAIL
Alex Phone #: ###-####- insulation shield on b vent in garage needs 1" clearance- need to seal all boots to floor- need to insulate supply duct in crawl between joists- need framing complete around supply and return air in stairwell- need flue test gauge at zero
MEC18-03501 Final7/18/20187/19/20187/19/2018 9:22:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Teresa Costello- furnace a/c coil co ok
MEC18-03339 Final7/17/20187/19/20187/19/2018 9:05:49 AMAPASS
Please call the Owner, Kelli at ###-#### with a 30 minute heads up arrival time. Thank you! Phone #: ###-#### Inspection requested via web by David or K Cole- furnace coil co ok
MEC18-02125 Final7/18/20187/19/20187/19/2018 8:34:13 AMAPASS
Final Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
MEC16-02807 Mec-Aging Inspection7/19/20187/19/20187/19/2018 8:04:18 AM DONE
MEC16-02807 DOC - Permit Expired7/19/20187/19/20187/19/2018 8:04:08 AMAPASS
bldg permit expired
MEC17-03433 Mec-Aging Inspection7/19/20187/19/20187/19/2018 8:03:28 AM FAIL
still waiting on final inspection to be scheduled by contractor