FIR17-00700
| INSP-Final Inspection | 7/18/2018 | 7/19/2018 | 7/19/2018 9:18:54 AM | P | FAIL |
|
|
Three fire sprinklers are to close to the ceiling fans, at least 36 inches is required. Five of the dry sidewalls on level 1 are to close to the deck, sidewall heads need to be 4 to 6 inches down from the ceiling.