Inspections for the day of: Wednesday, July 2, 1997.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJoe Tawney
TitleFIRE INSPECTOR
Phone #340-1295
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD96-01738 INSP-Final Inspection7/1/19977/2/19977/2/1997 12:00:00 AMAPASS
07/01/97 406 - 8 -8:15 REINSP FOR FINAL OK FOR PERM OCC
BLD96-02261 INSP-Sprinkler Rough-in/Hydro7/1/19977/2/19977/2/1997 12:00:00 AMAPASS
07/01/97 406 - AT 9 A.M. WITNESTED TRIP TESTS OF 2 DP SYSTEMS AFTER SPLIT OF 1 SYST EACH SYST NOW LESS THAN 750 GAL. ALSO PICKED UP REVISED PLANS AND REV CA
BLD96-02389 INSP-Sprinkler Rough-in/Hydro7/2/19977/2/19977/2/1997 12:00:00 AMPFAIL
07/02/97 406 - FINAL FAIL SPKLR HEADS TOO CLOSE FRONT DOOR AND GUARD RA ON APPROVED PLANS ON SITE ANTI FREEZE LOOP CONTROL VLVS NOT MONITORED SIGNAGE FOR ACCESSIBLE RESRROOMS
BLD96-01238 INSP-Final Inspection7/1/19977/2/19977/2/1997 12:00:00 AMPFAIL
07/01/97 406 - HE SAID YOU WOULD MEET AT 2 O'CLOCK FINAL FAIL ALARM SYSTEM SUBMITTAL DUCT DET NOT HOOKED UP CAN NOT SEE FIRE DAMPERS TO VERIFY IF THEY CLOSE SPKLR SYSTEM OK