Inspections for the day of: Monday, July 2, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03281 Final7/2/20077/2/20077/2/2007 2:52:12 PMPCANC
Please inspect 1st and 2nd floor of A-wing ceiling cover. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend called already done on added r/i 06-29-07
ELE07-02325 Rough-In Permanent Service7/2/20077/2/20077/2/2007 2:51:02 PMPPASS
Scheduled by a contractor via Hello! on 7/2/2007 at 10:59:55 AM. Contact: ###-####. r/i p/s u/g new ok
ELE07-02299 Electrical Rough-In7/2/20077/2/20077/2/2007 2:19:52 PMPPART
terry; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
conference on p/s no SER allowed in conduit, needs 3/0 copper or 250KC mil for 400 amp feeder, r/i for back office and restrm area ok walls and hard ceilings
ELE07-02316 Electrical Rough-In7/2/20077/2/20077/2/2007 1:33:52 PMPPART
ufer inspection. had to make one mudder forgot thanks joe. Phone #: ###-#### Internet Inspection Request from: joe wheeler electrode ok for concrete cover
ELE07-02108 Final7/2/20077/2/20077/2/2007 1:06:38 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ok
ELE07-02313 Electrical Rough-In7/2/20077/2/20077/2/2007 12:43:21 PMPFAIL
electrician is Tony Norton, service relocated and shop rough in Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer corr. do not cover posted called left message110.12(A) seal KOs, BCC needs concrete encased electrode, no violations retained 110.3(B) only manufactures listed breakers, subpanel, 314.43 no nails allowed in plastic boxes, 300.4(A)(1) nail plates above subpanel, 230.24(A) except. #3 needs 18" from roof to drip loop, 250.24(A)(5) isolate grds and neutrsals subpanel, 250.24(A)(1) or 104(A)(1) grd or bond water system?
ELE06-00711 Electrical Rough-In6/29/20077/2/20077/2/2007 11:07:54 AMAPART
Scheduled by a contractor via Hello! on 6/29/2007 at 10:05:24 AM. Contact: ###-####. 2nd floor completed ceilings ok, 4th floor roof garden and completed grid ceilings anop
ELE07-02245 Electrical Rough-In6/29/20077/2/20077/2/2007 9:58:16 AMAPART
Building branch underground Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton u/g ok
ELE07-02005 Permanent Service7/1/20077/2/20077/2/2007 9:38:02 AMAPASS
Scheduled by a contractor via Hello! on 7/1/2007 at 10:15:18 PM. Contact: ###-####. p/s u/g new ok
ELE07-02337 Permanent Service6/29/20077/2/20077/2/2007 9:18:57 AMAPASS
EDDIE ###-#### p/s u/g rec. ok
ELE07-02337 Final7/2/20077/2/20077/2/2007 9:18:17 AMAPASS
EDDIE ###-#### ok
ELE07-01840 Final6/29/20077/2/20077/2/2007 8:53:11 AMAPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ok card signed
ELE07-01588 Final6/29/20077/2/20077/2/2007 8:26:16 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok
ELE07-01587 Final6/29/20077/2/20077/2/2007 8:25:58 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok
ELE07-02245 Electrical Rough-In6/28/20077/2/20076/29/2007 3:21:03 PMPCANC
Underground
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
ELE07-02245 Electrical Rough-In6/28/20077/2/20076/28/2007 1:56:57 PMACANC
Underground Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton