Inspections for the day of: Monday, July 2, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01065 Temporary Service7/2/20077/2/20077/2/2007 3:43:15 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham corrections not made
ELE07-01601 Electrical Rough-In7/2/20077/2/20077/2/2007 3:12:57 PMPFAIL
Need grid cover inspection Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called, left corr notice, per nec 300.11(A) and BCC there shall be no cable on grid
ELE07-01321 Electrical Rough-In6/29/20077/2/20077/2/2007 2:52:30 PMPPASS
matt - ceiling grid; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang west end 2nd floor ceiling only except x-ray room ok to cover
ELE07-02235 Rough-In Permanent Service7/2/20077/2/20077/2/2007 2:23:25 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham see ri and p/s
ELE07-02235 Electrical Rough-In7/2/20077/2/20077/2/2007 2:07:35 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham called,no answer, nec 210.52(A)(1) shall install recpts such that no point along wall line is over 6' from an outlet ( front entry)
ELE07-02235 Permanent Service7/2/20077/2/20077/2/2007 2:03:09 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham p/s u/g n ok
ELE07-02067 Electrical Rough-In7/2/20077/2/20077/2/2007 1:41:20 PMPPASS
Glen; Phone #: ###-#### Internet Inspection Request from: Darla Downs east 1/2 walls only except break room ok to cover
ELE07-01551 Electrical Rough-In6/29/20077/2/20077/2/2007 1:05:03 PMPPASS
joe; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to cover 1st floor common area walls only anop
ELE07-02113 Final7/2/20077/2/20077/2/2007 12:24:01 PMPPASS
Corrections have been made. Ready for final. Chad will be there this afternoon. Call Dan with any questions. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final,
ELE07-02339 Electrical Rough-In6/29/20077/2/20077/2/2007 11:15:17 AMACANC
rough in walls & ceiling cover. Call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called contr wrong permit or bldg
ELE07-02326 Electrical Rough-In6/28/20077/2/20077/2/2007 10:58:37 AMAFAIL
jason Phone #: ###-#### called, left message, 219.52(A)(1) recpts shall be installed such that no point along wall is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member
ELE07-02312 Rough-In Permanent Service6/30/20077/2/20077/2/2007 10:16:24 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla corrections made, ric ok, p/s u/g n ok
ELE07-02299 Electrical Rough-In6/29/20077/2/20077/2/2007 9:38:06 AMACANC
terry Phone #: ###-#### see conf
ELE07-02299 Conference7/2/20077/2/20077/2/2007 9:37:56 AMADONE
terry Phone #: ###-#### met contr, reviewed 6" free conductor, not using valley of 2x4 steel stud for securing mc, make-up, inspections required, this is first time contr working in city
ELE07-02342 Electrical Rough-In6/29/20077/2/20077/2/2007 9:16:36 AMACANC
Inspection for underslab with floor box locations. Please schedule to inspect late morning Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE07-01831 Rough-In Permanent Service6/29/20077/2/20077/2/2007 9:04:29 AMAPASS
daryl Phone #: ###-#### ric house only, garages will be called for ltr, p/s u/g n ok
ELE07-02325 Electrical Rough-In6/29/20077/2/20077/2/2007 8:31:31 AMAFAIL
zane Phone #: ###-#### called contr, nec 210.52(A)(2) shall install recpt in 2' wall in kitchen and top of stairs, BCC no u/g to garage done
ELE07-01332 Final7/2/20077/2/20077/2/2007 7:58:39 AMAPASS
Scheduled by a contractor via Hello! on 7/2/2007 at 6:13:37 AM. Contact: ###-####. called for a/c label in panel, ok to final