Inspections for the day of: Wednesday, July 2, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01735 Conference7/2/20087/2/20087/2/2008 3:15:30 PMPDONE
met J Schmer at site talked to contr. about having journeyman at site while work is being done
ELE08-00186 Final7/2/20087/2/20087/2/2008 3:13:28 PMPPASS
ok job is now being done by new contr , permit #ele08-01735
ELE08-01353 Rough-In Permanent Service7/1/20087/2/20087/2/2008 2:42:32 PMPPASS
Internet Inspection Request from: Stephen Kren r/i p/s u/g new ok
ELE08-01302 Final7/1/20087/2/20087/2/2008 2:01:15 PMPPASS
I''ll have to meet you and let you in , they have a dog and will not be home. Phone #: ###-#### Internet Inspection Request from: Andy Derrick ok needs extension box for pen. counter recept box too small contr will correct
ELE07-04131 Electrical Rough-In7/1/20087/2/20087/2/2008 1:37:44 PMPPART
Service inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean needs to request p/s inspection when ready corr posted met contr 110.26(F)(1) remove water pipe from above subpanel, and 250.104(A)(1) bond all water to p/s gear, terminate main bond and GEC to neutral at p/s
ELE08-01815 Permanent Service7/2/20087/2/20087/2/2008 12:26:34 PMPPASS
DON Phone #: ###-#### NOTE: SPACE 10
p/s u/g rec. ok
ELE08-01815 Final7/2/20087/2/20087/2/2008 12:26:11 PMPPASS
DON Phone #: ###-#### NOTE: SPACE 10
ok
ELE08-01690 Permanent Service7/1/20087/2/20087/2/2008 11:39:35 AMAPASS
just want to heat up service Phone #: ###-#### Internet Inspection Request from: John Edwards p/s u/g for meter ok
ELE08-01738 Final7/1/20087/2/20087/2/2008 10:22:35 AMACANC
Need ceiling grid inspection Phone #: ###-#### Internet Inspection Request from: Lloyd Looney see added r/i
ELE08-01738 Electrical Rough-In7/2/20087/2/20087/2/2008 10:22:12 AMAPART
Need ceiling grid inspection Phone #: ###-#### Internet Inspection Request from: Lloyd Looney ok
ELE08-01613 Permanent Service7/1/20087/2/20087/2/2008 10:05:27 AMAFAIL
Site combo is 9876. Call for access into Verizon Shelter to inspect inside if no one is on site.
called needs grd listed for wire size
Thanks Phone #: ###-#### Internet Inspection Request from: Donovan Waldenmyer
ELE08-01590 Final7/1/20087/2/20087/2/2008 9:31:53 AMAPASS
READY Phone #: ###-#### Internet Inspection Request from: Bob Glennok card signed
ELE08-00946 ELE-Aging Inspection7/2/20087/2/20087/2/2008 9:19:17 AM DONE
wsuc
ELE08-00455 ELE-Aging Inspection7/2/20087/2/20087/2/2008 9:18:59 AM DONE
still waiting for contr to schedule inspection and access
ELE08-01681 Rough-In Permanent Service7/1/20087/2/20087/2/2008 8:44:16 AMAPASS
SORRY JACK.... SOME PEOPLE''S KIDS.. BUY EM BOOKS, SEND EM TO SCHOOL AND THIS IS WHAT YOU GET.......FRUSTRATING!!! ITS FIXED NOW Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/ip/s u/g new ok
ELE08-01799 Temporary Service7/1/20087/2/20087/2/2008 8:12:12 AMAPASS
THANK YOU Phone #: ###-#### Internet Inspection Request from: Bob Glenn
t/s u/g new ok