FIR07-01018
| INSP-Sprinkler Rough-in/Hydro | 7/1/2008 | 7/2/2008 | 7/2/2008 4:34:13 PM | P | FAIL |
|
|
OH rough-in inspection failed due to several items including 1st floor overspaced corner, elevator pit SW too high, noted added heads at entry vestibule, relocate EQ brace at office 103 if intended for the adjacent main longitudinal-see detail on plan set, warehouse area is missing proper temp. heads at the unit heater zones (13), noted two added heads and two deleted heads not required due to construction changes, one overspaced corner at the warehouse, 2nd floor office area missing two ssu heads, mixed temp. at one area, 4 heads exceed min. spacing, an additonal corner is overspaced. See locations marked in red on approved plan set for defficiencies. NOTE: Overhead hydrostatic test for both wet systems passed.
|
BLD07-00133
| FIRE-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 4:30:33 PM | P | PASS |
|
|
Final inspection completed. KR
|
BLD07-03107
| FIRE-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 4:29:53 PM | P | PASS |
|
|
Final inspection completed.KR
|
BLD08-01112
| FIRE-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 2:54:45 PM | P | FAIL |
|
|
C/N items are complete with the exception of data cable run in the plenum without a raceway, conduit or plenum rating-see on site correction notice issued per J. Schmer electrical division.
|
BLD08-01113
| FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 2:50:59 PM | P | PASS |
|
|
Fire life safety passed.
|
FIR07-00956
| INSP-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 2:12:32 PM | P | PASS |
|
|
Fire sprinkler inspection complete as per Forrest. KR
|
BLD07-00813
| FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 2:10:55 PM | A | CANC |
|
|
Will call it in for next monday 7/7/08 NOTE: Also missing project related fire sprinkler permit final to be completed prior to building fire life safety approval and final inspection.
|
BLD06-01994
| FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 1:54:23 PM | A | DEFR |
|
|
AM inspections overbooked, contractor rescheduled for 7/3 per agreement.
|
BLD06-01992
| FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 1:53:30 PM | A | DEFR |
|
|
AM inspections overbooked, contractor rescheduled for 7/3 per agreement.
|
FIR08-00422
| INSP-Sprinkler Rough-in | 7/1/2008 | 7/2/2008 | 7/2/2008 1:45:24 PM | A | FAIL |
|
|
Need to provide area separation at four locations (mechanical closets without a drop ceiling or walls extending to the deck), one pendent head is too close to an adjacent wall, one existing armover hanger needs to be repaired. The remainder of overhead work and head change out completed satisfactory.
|
FIR08-00385
| INSP-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 1:19:15 PM | A | PASS |
|
|
Final fire sprinkler inspection completed. KR
|
FIR08-00110
| INSP-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 1:03:50 PM | A | PASS |
|
|
Fire alarm permit work passed field testing including new nac panel, duct smokes, initiation and notification appliances, minor field modifications accepted, incorrect descriptor at one duct detector FCU 3 amended while on site, signal report okay, fire alarm permit finaled.
|
FIR08-00109
| INSP-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 12:59:26 PM | A | PART |
|
|
Nac, duct detectors, ID detectors, notification and initiation devices tested today throughout the tenant improvement area, noted one obstructed a/v at the file storage area (see plan review annotation), missing junction box cover above the nac panel, signals verified okay, final pending file room coverage adjustments and NFPA 72 forms for signature.
|
BLD08-00118
| FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 12:27:37 PM | A | FAIL |
|
|
Door hardware for restrooms need to be changed see item#4 on fire plan review comments for correct hardware requirments. Suite address needs to be posted at main entrance. KR
|
BLD08-00502
| FIRE-Final Inspection | 7/1/2008 | 7/2/2008 | 7/2/2008 12:03:55 PM | A | FAIL |
|
|
Exit light in rear storage room did not function, Egress lights were not installed and are required based on occupancy load. KR
|
FIR07-01031
| INSP-Sprinkler Rough-in | 7/1/2008 | 7/2/2008 | 7/2/2008 11:26:21 AM | A | PART |
|
|
See redlined areas on city approved plans for areas ok to cover. KR
|
FIR08-00038
| FIR-Aging Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 9:14:52 AM | | DEFR |
|
|
Pending site inspection request for work completed.
|