FIR12-00033
| INSP-Alarm Testing | 6/28/2012 | 7/2/2012 | 7/6/2012 7:06:09 AM | P | FAIL |
|
|
The wall mount notification appliance at the new conference room second floor west side is not listed to be installed on the ceiling. Discussed scope of alarm permit work and extent of modifications to be completed at this time. Upgrade to current NFPA 72 standards at existing areas to follow under future permits. Also discussed project schedule and inspection appointments.
|
FIR12-00246
| INSP-Sprinkler Rough-in | 7/2/2012 | 7/2/2012 | 7/2/2012 3:52:39 PM | P | PART |
|
|
Tenting at the wet system lines west wing only approved as noted.
|
FIR12-00217
| INSP-Final Inspection | 6/29/2012 | 7/2/2012 | 7/2/2012 3:50:11 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions. Permit finaled.
|
BLD12-00695
| FIRE-Conference | 7/2/2012 | 7/2/2012 | 7/2/2012 3:11:54 PM | A | DONE |
|
|
Regarding existing partial overhead fire sprinkler system.
|
BLD12-00746
| FIRE-Final Inspection | 6/29/2012 | 7/2/2012 | 7/2/2012 3:10:05 PM | A | PASS |
|
|
Noted conditions for final occupancy field verified for completion. Life safety final approved.
|