BLD11-01268
| FIRE-Final Inspection | 7/2/2012 | 7/2/2012 | 7/2/2012 3:46:28 PM | P | CANC |
|
|
Area "B" 3rd and 4th floors life safety will be a pass when the project related fire alarm system for this area is tested. Smoke alarms tested.
|
BLD11-01267
| FIRE-Final Inspection | 7/2/2012 | 7/2/2012 | 7/2/2012 3:28:44 PM | A | FAIL |
|
|
Area "A" 3rd and 4th floors life safety will be a pass when the project related fire alarm system for this area is tested. Smoke alarms tested.
|
FIR11-00621
| INSP-Final Inspection | 7/2/2012 | 7/2/2012 | 7/2/2012 3:14:50 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00262
| INSP-Sprinkler Rough-in | 7/2/2012 | 7/2/2012 | 7/2/2012 3:13:07 PM | P | PART |
|
|
Sprinkler piping is ok to cover. One pendant was adjusted while I was there. Sprinkler coverage needs to be provided in the empty tenant space along the new demising wall.
|
FIR12-00223
| INSP-Sprinkler Rough-in/Hydro | 7/2/2012 | 7/2/2012 | 7/2/2012 3:11:24 PM | P | PART |
|
|
Hydro test passed. Sprinkler piping above the lay-in ceiling tile is ok to cover. Plans and hydraulic calculations need to be resubmitted showing the 1 1/4" far main. The plans and calculations show the piping as 1 1/2" piping. Need the pressure relief valve installed.
|