Inspections for the day of: Wednesday, July 20, 2005.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00531 INSP-Final Inspection7/19/20057/20/20057/20/2005 3:45:50 PMAFAIL
Need to verify that the exposed combustibles located above the outside canopies has met requirements of NFPA 13 for combustible concealed spaces.
BLD05-00634 FIRE-Conference7/15/20057/20/20057/20/2005 3:25:05 PMPDONE
Met with the other inspectors and the building contractor and went over general procedures for inspection and sign offs.
BLD05-00287 FIRE-Final Inspection7/20/20057/20/20057/20/2005 3:20:34 PMPFAIL
Provide indicators on the door locks at the main exit per review comments #10. Provide sticker at the main exits per review comment #10. Provide atleast four 2A fire extinguishers or two 4A fire extinguishers per review comment #5 and verbal agreement.
BLD05-00886 FIRE-Final Inspection7/19/20057/20/20057/20/2005 12:54:45 PMAPASS
fire life safety finaled
FIR03-00624 INSP-Final Inspection7/13/20057/20/20057/20/2005 9:02:03 AMAPASS
Permit finaled