Inspections for the day of: Friday, July 20, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00011 INSP-Alarm Testing7/20/20077/20/20077/23/2007 5:43:43 PMPPASS
See the city approved plans for Mike Timmermans progress.
BLD05-03359 FIRE-Final Inspection7/19/20077/20/20077/20/2007 5:17:36 PMPFAIL
The contractor needs to provide the interlocks as per chapter 15 of the IFC
FIR07-00103 INSP-Sprinkler Rough-in/Hydro7/20/20077/20/20077/20/2007 5:16:38 PMPPASS
Hydro Test of the second floor passed.
FIR07-00501 INSP-Sprinkler Rough-in7/19/20077/20/20077/20/2007 5:15:44 PMPPASS
See the city approved plans for the location where the sprinkler piping can be covered by the hard lids.
FIR05-00536 INSP-Sprinkler Rough-in/Hydro7/19/20077/20/20077/20/2007 5:14:22 PMAPASS
The hydro test of the east and west systems of the second floor has passed.
FIR07-00540 INSP-Final Inspection7/19/20077/20/20077/20/2007 1:29:06 PMPFAIL
The releasing panel would not trip the valve. The required second permit for the two panel interconnecton was not called in and was not tested. I did test the some of the smoke detectors and all of the manual pulls. But this test really should be started over.
FIR07-00427 INSP-Sprinkler Rough-in7/19/20077/20/20077/20/2007 1:04:39 PMAFAIL
The inspection was for an underground cover but the contact did not answer repeated phone calls and no plans were readily available.
FIR07-00377 INSP-Sprinkler Rough-in7/18/20077/20/20077/20/2007 12:45:29 PMAPASS
See the city approved plans for the locations where the sprinkler piping can be covered. I found one pipe in the restroom appears to be leaking. I pointed this out to dave the fitter.
BLD06-02700 FIRE-Final Inspection7/19/20077/20/20077/20/2007 11:49:55 AMAPASS
Life safety passed
BLD07-00064 FIRE-Final Inspection7/19/20077/20/20077/20/2007 11:10:35 AMAPART
A temporary occupancy was given. The exit sign and emergency light in the kitchen needs repaired. The two hvac units that required duct smoke detectors had the sample tubes installed backwards and have not been tested yet. The contractor locked out the units so they would not operate. This is a condition of the temporary.
FIR07-00513 INSP-Final Inspection7/19/20077/20/20077/20/2007 10:10:50 AMAPASS
Permit finaled. The pizza oven has been approved by Lee Rice to not have the type 1 hood therefore no suppression system.
FIR07-00608 INSP-Sprinkler Rough-in7/19/20077/20/20077/20/2007 9:01:28 AMAFAIL
I arrived at the project but my contact was tied up on the phone. I waited abit then left.
BLD06-00920 FIRE-Final Inspection7/19/20077/20/20077/20/2007 8:30:06 AMAPASS
Life safety passed
BLD06-00919 FIRE-Final Inspection7/19/20077/20/20077/20/2007 8:29:32 AMAPASS
Life safety passed
BLD06-00918 FIRE-Final Inspection7/19/20077/20/20077/20/2007 8:27:52 AMAPASS
Life safety passed
BLD06-00946 FIRE-Final Inspection7/19/20077/20/20077/20/2007 8:27:20 AMAPASS
LIfe safety passed