FIR06-00011
| INSP-Alarm Testing | 7/20/2007 | 7/20/2007 | 7/23/2007 5:43:43 PM | P | PASS |
|
|
See the city approved plans for Mike Timmermans progress.
|
BLD05-03359
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 5:17:36 PM | P | FAIL |
|
|
The contractor needs to provide the interlocks as per chapter 15 of the IFC
|
FIR07-00103
| INSP-Sprinkler Rough-in/Hydro | 7/20/2007 | 7/20/2007 | 7/20/2007 5:16:38 PM | P | PASS |
|
|
Hydro Test of the second floor passed.
|
FIR07-00501
| INSP-Sprinkler Rough-in | 7/19/2007 | 7/20/2007 | 7/20/2007 5:15:44 PM | P | PASS |
|
|
See the city approved plans for the location where the sprinkler piping can be covered by the hard lids.
|
FIR05-00536
| INSP-Sprinkler Rough-in/Hydro | 7/19/2007 | 7/20/2007 | 7/20/2007 5:14:22 PM | A | PASS |
|
|
The hydro test of the east and west systems of the second floor has passed.
|
FIR07-00540
| INSP-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 1:29:06 PM | P | FAIL |
|
|
The releasing panel would not trip the valve. The required second permit for the two panel interconnecton was not called in and was not tested. I did test the some of the smoke detectors and all of the manual pulls. But this test really should be started over.
|
FIR07-00427
| INSP-Sprinkler Rough-in | 7/19/2007 | 7/20/2007 | 7/20/2007 1:04:39 PM | A | FAIL |
|
|
The inspection was for an underground cover but the contact did not answer repeated phone calls and no plans were readily available.
|
FIR07-00377
| INSP-Sprinkler Rough-in | 7/18/2007 | 7/20/2007 | 7/20/2007 12:45:29 PM | A | PASS |
|
|
See the city approved plans for the locations where the sprinkler piping can be covered. I found one pipe in the restroom appears to be leaking. I pointed this out to dave the fitter.
|
BLD06-02700
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 11:49:55 AM | A | PASS |
|
|
Life safety passed
|
BLD07-00064
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 11:10:35 AM | A | PART |
|
|
A temporary occupancy was given. The exit sign and emergency light in the kitchen needs repaired. The two hvac units that required duct smoke detectors had the sample tubes installed backwards and have not been tested yet. The contractor locked out the units so they would not operate. This is a condition of the temporary.
|
FIR07-00513
| INSP-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 10:10:50 AM | A | PASS |
|
|
Permit finaled. The pizza oven has been approved by Lee Rice to not have the type 1 hood therefore no suppression system.
|
FIR07-00608
| INSP-Sprinkler Rough-in | 7/19/2007 | 7/20/2007 | 7/20/2007 9:01:28 AM | A | FAIL |
|
|
I arrived at the project but my contact was tied up on the phone. I waited abit then left.
|
BLD06-00920
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 8:30:06 AM | A | PASS |
|
|
Life safety passed
|
BLD06-00919
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 8:29:32 AM | A | PASS |
|
|
Life safety passed
|
BLD06-00918
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 8:27:52 AM | A | PASS |
|
|
Life safety passed
|
BLD06-00946
| FIRE-Final Inspection | 7/19/2007 | 7/20/2007 | 7/20/2007 8:27:20 AM | A | PASS |
|
|
LIfe safety passed
|